PAGE 20 — DCA12SSIU4F 60 HZ GENERATOR • OPERATION MANUAL — REV. #0 (07/20/17)
OUTPUT TERMINAL PANEL FAMILIARIZATION
OUTPUT TERMINAL PANEL
The Output Terminal Panel (Figure 7) shown below is
provided for the connection of electrical loads. Lift up on
the cover to gain access to receptacles and terminal lugs.
NOTICE
Terminal legs “O” and “Ground” are considered bonded
grounds
OUTPUT TERMINAL FAMILIARIZATION
The “Output Terminal Panel” (Figure 7) is provided with
the following:
Three (3) 240/139V output receptacles @ 50 amp
Three (3) Circuit Breakers @ 50 amps
Two (2) 120V GFCI receptacles @ 20 amp
Two (2) Duplex Circuit Breakers @ 20 amp
Five (5) Output Terminal Lugs (U, V, W, O, Ground)
AUX. POWER RECEPTACLES
240/120V, 50 AMPS
120 VAC, 20 AMP
GFCI RECEPTACLES
Y
X
W
CS-6369
TWIST-LOCK
CIRCUIT BREAKERS
FOR GFCI RECEPTACLES
RECEPTACLE
AND
CIRCUIT BREAKER
PANEL
ACCESS DOOR
LIFT TO OPEN
HARD WIRE
HOOKUP PANEL
O
U
V
W
BLACK
RED
BLUE
WHITE
GREEN
1Ø AND 3Ø,
480 -120 VAC
OUTPUT TERMINALS
NEUTRAL
TERMINAL
GROUND
TERMINAL
CIRCUIT BREAKERS
FOR CS-6369 TWIST
LOCK RECEPTACLES
Figure 7. Output Terminal Panel