TROUBLESHOOTING AND REPAIR
37
CF11 CF12
CF22
G
CF32
CF31 J3
G
Inspection of Compressor Motor
Inspection of Evaporator Fan Motor
Inspection of Condenser Fan Motor
21. Inspection of Condenser Fan Motor
Measure resistance across the terminals of the
fan motor.
Terminals (at 77˚F (25˚C))
J3-CF32
Approx. 9.0
Ω
J3-CF31
Approx. 8.83
Ω
CF31-CF32
Approx. 18
Ω
If the measured resistance does not approxi-
mately equal these standard values
±
10%,
replace the fan motor.
22. Inspection of Evaporator Fan Motor
Measure resistance across the terminals of the
fan motor.
Terminals (at 77˚F (25˚C))
CF11-CF22
Approx. 52.8
Ω
CF22-CF12
Approx. 50.7
Ω
If the measured resistance does not approxi-
mately equal these standard values
±
10%,
replace the fan motor.
23. Inspection of Compressor Motor
Measure resistance across the terminals of the
compressor motor.
Terminals (wire tag) at 77˚F (25˚C)
R-C (CC1-J4)
Approx. 1.0
Ω
C-S (J4-CC2)
Approx. 2.2
Ω
S-R (CC2-CC1)
Approx. 3.0
Ω
If the measured resistance does not approxi-
mately equal these standard values
±
10%,
replace the compressor.
24. Inspection of Wiring Connection
Refer to the Wiring Diagrams on page 45 and
check for connection of each wire.
25. Inspection of Thermistor
Using an Ohmeter, check the resistance value
across the 2-pin connector. At normal tempera-
ture (77˚F (25˚C)) either thermistor (room or freeze)
should measure approximately 10,000 or 10K
ohms.
Summary of Contents for Office Pro 10
Page 1: ...SERVICE MANUAL OFFICE PRO 10...
Page 3: ...SERVICE MANUAL OFFICE PRO 10...
Page 4: ......
Page 6: ...ii...
Page 8: ...iv...
Page 10: ...2 GENERAL DESCRIPTION...
Page 54: ...TROUBLESHOOTING AND REPAIR 46...
Page 56: ...800 264 9573 www movincool com DSCA P N LA990009 1196...