7.4.7.
Control Menu
This chapter describes the features and configuration options of the control inputs. Depending on
the operating mode (see chapter
), up to two HTL/PNP control inputs (Control1 and Control2) are
available at terminal [X10 | CONTROL IN].
Control1
X10 | CONTROL IN, Pin 2, 3
Control2
X10 | CONTROL IN, Pin 4, 5
A control input can only be used, if Control1 or Control2 (see chapter
, et seq.) is available in the
selected operation mode.
For security reasons both control inputs are complementary. The switching conditions (active HIGH
or active LOW) can be defined by parameter 063.
Basically always the complementary signal of the direct input must be applied to the inverted input.
All other conditions are invalid and will not be accepted by the unit. Valid conditions are:
Control1
X10 | CONTROL IN, Pin 2, HIGH
X10 | CONTROL IN, Pin 3, LOW
X10 | CONTROL IN, Pin 2, LOW
X10 | CONTROL IN, Pin 3, HIGH
Control2
X10 | CONTROL IN, Pin 4, HIGH
X10 | CONTROL IN, Pin 5, LOW
X10 | CONTROL IN, Pin 4, LOW
X10 | CONTROL IN, Pin 5, HIGH
If the commands „Set Frequency“ and „Freeze Frequency“ are activated simultaneously by the
external control inputs, the function „Set Frequency“ has priority.