Ca306_01d_oi_e.doc / Apr-16 

 

Page 4 / 10 

1.3.

 

Installation 

The device is only allowed to be installed and operated within the permissible temperature 
range. Please ensure an adequate ventilation and avoid all direct contact between the device 
and hot or aggressive gases and liquids.  

 

Before installation or maintenance, the unit must be disconnected from all voltage-sources. 
Further it must be ensured that no danger can arise by touching the disconnected voltage-
sources.

 

 

Devices which are supplied by AC-voltages, must be connected exclusively by switches, 
respectively circuit-breakers with the low voltage network. The switch or circuit-breaker must 
be placed as near as possible to the device and further indicated as separator. 

 

Incoming as well as outgoing wires and wires for extra low voltages (ELV) must be separated 
from dangerous electrical cables (SELV circuits) by using a double resp. increased isolation. 

 

All selected wires and isolations must be conform to the provided voltage- and temperature-
ranges. Further all country- and application-specific standards, which are relevant for structure, 
form and quality of the wires, must be ensured. Indications about the permissible wire cross-
sections for wiring are described in the Technical Specifications (see chapter 

10

).  

 

Before first start-up it must be ensured that all connections and wires are firmly seated and 
secured in the screw terminals. All (inclusively unused) terminals must be fastened by turning 
the relevant screws clockwise up to the stop.  

 

Overvoltages at the connections must be limited to values in accordance to the overvoltage 
category II.  

 

For placement, wiring, environmental conditions as well as shielding and earthing/grounding of 
the supply lines the general standards of industrial automation industry and the specific 
shielding instructions of the manufacturer are valid.  

 

Please find all respective hints and rules on 

www.motrona.com/download.html   

--> “[General EMC Rules for Wiring, Screening and Earthing]”. 
 

1.4.

 

Cleaning, Maintenance and Service Notes 

To clean the front of the unit please use only a slightly damp (not wet!), soft cloth. For the rear 
no cleaning is necessary. For an unscheduled, individual cleaning of the rear the maintenance 
staff or assembler is self-responsible.  

 

During normal operation no maintenance is necessary. In case of unexpected problems, failures 
or malfunctions the device must be shipped for back to the manufacturer for checking, 
adjustment and reparation (if necessary). Unauthorized opening and repairing can have 
negative effects or failures to the protection-measures of the unit.   

Summary of Contents for CA306

Page 1: ...a simple data preset unit with a BCD coded thumbwheel switch The unit allows an easy remote setting of single parameters e g speed setting of a drive via fieldbus By pressing the ENTER button the actual BCD setting will be transmitted to the selected register of the target unit as SDO Service Data Object For data transmission as PDO Process Data Object according to CiA DS 301 our alternative versi...

Page 2: ...tion usage or publication in other electronic and printed media as well as in the internet requires prior written authorization by motrona GmbH Table of Contents 1 Safety Instructions and Responsibility 3 1 1 General Safety Instructions 3 1 2 Use according to the intended purpose 3 1 3 Installation 4 1 4 Cleaning Maintenance and Service Notes 4 2 Introduction 5 3 Block diagram 5 4 Connections 6 5 ...

Page 3: ...he right to modify the hardware software or operation manual at any time and without prior notice Therefore there might be minor differences between the unit and the descriptions in operation manual The raiser respectively positioner is exclusively responsible for the safety of the system and equipment where the unit will be integrated During installation or maintenance all general and also all co...

Page 4: ... sections for wiring are described in the Technical Specifications see chapter 10 Before first start up it must be ensured that all connections and wires are firmly seated and secured in the screw terminals All inclusively unused terminals must be fastened by turning the relevant screws clockwise up to the stop Overvoltages at the connections must be limited to values in accordance to the overvolt...

Page 5: ... Option VZ000 the unit is supplied as version with 5 digits sign preset range 99 999 99 999 Both versions are suitable for communication on the CANopen parameter channel accessing adjustable register codes of a network participant For operation on the process data level the special PDO version CA307 is available 3 Block diagram 1 2 3 4 1 2 3 4 5 6 7 8 LED ENTER Prozessor and CAN controller Potenti...

Page 6: ...the supply voltage 60 50 40 30 20 10 10 20 30 40 mA Volt The following cables are recommended for CAN communication depending on the cable length Up to 300 meters Cable type LIYCY 2 x 2 x 0 5 mm twisted and screened Resistance 40 km Capacity 130 nF km More than 300 meters Cable type CYPIMF 2 x 2 x 0 5 mm twisted and screened Resistance 40 km Capacity 60 nF km Please use the leads like shown Pair 1...

Page 7: ...5 Setting of the network Baud rate and sign Depending on the Baud rate the following maximum cable length must not be exceeded maximum cable length Baud rate kbit s 50 125 250 500 1000 Cable length m 1000 550 250 110 25 Setting the baud rate uses positions 1 to 3 of the 4 position DIL switch on the rear 4 1 2 3 1 2 3 4 5 6 7 8 GND G C C 0 0 0 1 0 0 0 1 0 1 1 1 1 1 1 1 1 1 1 0 0 0 0 0 Baud Baud Bau...

Page 8: ...ter power down by transmitting Store EEPROM to Code C003 Slider 7 and 8 determine the register codes to be accessed in the target unit Codes shown in subsequent list refer to LENZE series 9300 drives Other code classifications are possible at any time Important note All DIL switch settings are only read upon initialization and changes during normal operation will not be recognized After change of ...

Page 9: ...n be reset by pressing the Enter button To reset Error 1 it is necessary to switch off the unit and power up again 8 Transmission details The unit transmits the data by SDO Service Data Object Write Request and awaits a corresponding Write Response within the next 2 5sec Timeout It operates similar to a CANopen master But it is no CANopen master No other CANopen communication objects are supported...

Page 10: ...20 50 125 250 500 1000 kbit s BCD switch Preset range 0 999 999 standard 99 999 99 999 Option VZ000 Housing Material Mounting Dimensions Protection class Weight plastic panel outer dimensions w x h x d 96 x 48 x 120 mm 3 78 x 1 89 x 4 72 inch cut out w x h 92 x 43 mm 3 62 x 1 69 inch front IP 40 rear IP20 IP65 is available as an option approx 250 g Temperature range Operation Storage 0 C 45 C 32 1...

Reviews: