Group 11- Performance Control Functions
No.
Description
Range
Factory
Setting
unit
Note
11-10
Skip Frequency 3
0.00 ~ 599.00
0.00
Hz
*1
11-11
Skip Frequency Range
Bandwith (±)
0.00 ~ 30.00
0.00
Hz
*1
11-12
Energy Saving Gain (V/F
Mode)
0 ~ 100
80
%
11-13
Regeneration Prevention
Function
0:Disable
0
-
1:Enable
2:Enable (only during constant speed)
11-14
Regeneration Prevention
Voltage Level
200V:300.0~400.0
380.0
V
400V:600.0~800.0
760.0
11-15
Regeneration Prevention
Frequency Limit
0.00 ~ 15.00
3.00
Hz
11-16
Regeneration Prevention
Voltage Gain
0~200
100
%
11-17
Regeneration Prevention
Frequency Gain
0~200
100
%
Group 12 Digital Display & Monitor Functions
No.
Description
Range
Factory
Setting
Unit
Note
12-00
Extended Display Mode
00000~88888
Each digit can be set from 0 to 8 as
listed below.
00000
-
*1
0: Default Display
(Frequency and Parameters)
1:Output Current
2:Output Voltage
3:DC Voltage
4:Temperature
5:PID Feedback
6:Analog Signal Input. (AI1)
7:Analog Signal Input. (AI2)
8: Count Status
12-01
PID Feedback Display
Format
0:Integer (xxx)
0
-
*1
1:One Decimal Place (xx.x)
2:Two Decimal Places (x.xx)
12-02
PID Feedback Display Unit
Setting
0:xxx--
0
-
*1
1:xxxpb(pressure)
2:xxxfl(flow)
12-03
Custom Units (Line Speed)
Value
0~65535
1500/1800
RPM
*1
12-04
Custom Units (Line Speed)
Display Mode
0:Drive Output Frequency is Displayed
0
-
*1
1:Line Speed.Integer.(xxxxx)
2:Line Speed.One Decimal Place.
(xxxx.x)
3:Line Speed.Two Decimal Places
(xxx.xx)
4:Line Speed.Three Decimal Places
(xx.xxx)