Motovario EM16-123 F-20 Series Manual Download Page 31

31

Group 05- Preset Frequency Selections

No.

Description

Range

Factory

Setting

Unit

Note

05-00

Preset Speed Control
Mode Selection

0: Common Accel/Decel

Accel/Decel 1 or 2 apply to all speeds

0

-

1: Individual Accel/Decel for each preset speed
0-15 apply to the selected preset speeds
(Acc0/Dec0~Acc15/Dec15)

05-01

Preset Speed 0
(Keypad Freq)

0.00 ~ 599.00

5.00

Hz

05-02

Preset Speed1

(Hz)

5.00

Hz

*1

05-03

Preset Speed2

(Hz)

10.00

Hz

*1

05-04

Preset Speed3

(Hz)

20.00

Hz

*1

05-05

Preset Speed4

(Hz)

30.00

Hz

*1

05-06

Preset Speed5

(Hz)

40.00

Hz

*1

05-07

Preset Speed6    (Hz)

50.00

Hz

*1

05-08

Preset Speed7    (Hz)

50.00

Hz

*1

05-09

Preset Speed8    (Hz)

0.00

Hz

*1

05-10

Preset Speed9    (Hz)

0.00

Hz

*1

05-11

Preset Speed10    (Hz)

0.00

Hz

*1

05-12

Preset Speed11    (Hz)

0.00

Hz

*1

05-13

Preset Speed12    (Hz)

0.00

Hz

*1

05-14

Preset Speed13    (Hz)

0.00

Hz

*1

05-15

Preset Speed14    (Hz)

0.00

Hz

*1

05-16

Preset Speed15    (Hz)

0.00

Hz

*1

05-17

Preset Speed0-Acctime

0.1 ~ 3600.0

10.0

Sec

*1

05-18

Preset Speed0-Dectime

10.0

Sec

*1

05-19

Preset Speed1-Acctime

10.0

Sec

*1

05-20

Preset Speed1-Dectime

10.0

Sec

*1

05-21

Preset Speed2-Acctime

10.0

Sec

*1

05-22

Preset Speed2-Dectime

10.0

Sec

*1

05-23

Preset Speed3-Acctime

10.0

Sec

*1

05-24

Preset Speed3-Dectime

10.0

Sec

*1

05-25

Preset Speed4-Acctime

10.0

Sec

*1

05-26

Preset Speed4-Dectime

10.0

Sec

*1

05-27

Preset Speed5-Acctime

10.0

Sec

*1

05-28

Preset Speed5-Dectime

10.0

Sec

*1

05-29

Preset Speed6-Acctime

10.0

Sec

*1

05-30

Preset Speed6-Dectime

10.0

Sec

*1

05-31

Preset Speed7-Acctime

10.0

Sec

*1

05-32

Preset Speed7-Dectime

10.0

Sec

*1

05-33

Preset Speed8-Acctime

10.0

Sec

*1

05-34

Preset Speed8-Dectime

10.0

Sec

*1

05-35

Preset Speed9-Acctime

10.0

Sec

*1

05-36

Preset Speed9-Dectime

10.0

Sec

*1

05-37

Preset Speed10-Acctime

10.0

Sec

*1

05-38

Preset Speed10-Dectime

10.0

Sec

*1

05-39

Preset Speed11-Acctime

10.0

Sec

*1

05-40

Preset Speed11-Dectime

10.0

Sec

*1

05-41

Preset Speed12-Acctime

10.0

Sec

*1

05-42

Preset Speed12-Dectime

10.0

Sec

*1

Summary of Contents for EM16-123 F-20 Series

Page 1: ...3 2 Single Three Phase 12 2 3 3 Three Phase 13 2 4 Terminal Description 14 2 4 1 Description of main circuit terminals 14 2 4 2 Control circuit terminal description 15 2 5 Outline Dimensions 16 2 5 1...

Page 2: ...rsonal injury if misused Caution Indicates that the inverter or the mechanical system might be damaged if misused Danger Risk of electric shock The DC link capacitors remain charged for five minutes a...

Page 3: ...ct provides the 24V for internal use only do not use as the power supply sources for other external components such as sensors electronic components etc otherwise it will cause adverse situation When...

Page 4: ...the run FWD REV switch closed then the inverter will restart Danger Prior to use ensure that all risks and safety implications are considered When the momentary power loss ride through is selected and...

Page 5: ...switched off before disassembling or checking any components 1 5 Inverter Disposal Caution Please dispose of this unit with care as an industrial waste and according to your required local regulation...

Page 6: ...00V 400V inverter with rating below 15KW is connected to a high capacity power source 600KVA or above then an AC reactor can be connected for power factor improvement and reducing harmonics Input nois...

Page 7: ...1850 EMI filter F integrated standard EMI filter A class C2 category IP degree 20 IP20 enclosure 66 IP66 enclosure Power supply 123 1ph 230V 340 3ph 400V Local command Blank No built in S Power Switc...

Page 8: ...sure IP20 The input current is calculated value at full rated output current F Built in EMI filter 20 Protection class IP20 Type Enclosure IP66 Power switch on board Potentiometer on board Model EM16...

Page 9: ...ry power loss time s 2 0 2 0 2 0 2 0 Enclosure IP20 The input current is calculated value at full rated output current Model EM16 340 F 20 0550 0750 1100 1500 1850 Recommended motor power KW 5 5 7 5 1...

Page 10: ...2 5 2 5 Allowable momentary power loss time s 2 0 2 0 2 0 2 0 Enclosure IP66 Model EM16 340 F 66 S 0550 0750 1100 Recommended motor power KW 5 5 7 5 11 Rated output current A 13 0 17 5 24 Rated power...

Page 11: ...on input 29 functions refer to description on group3 Multifunction output 21 functions refer to description on group3 Multifunction analog output 5 functions refer to description on group4 Main featur...

Page 12: ...brake transistor Communication control Standard built in RS485 communication Modbus One to one or One to many control Environment Operating temperature 10 50 Note1 Storage temperature 20 60 Humidity...

Page 13: ...13 2 3 Standard wiring 2 3 1 Single Phase Models EM16 123 0037 F EM16 123 0075 F EM16 123 0150 F EM16 123 0220 F...

Page 14: ...4 2 3 3 Three phase Multifunction Input Terminals Models EM16 340 0075 F EM16 340 0150 F EM16 340 0220 F EM16 340 0400 F EM16 340 0550 F EM16 340 0750 F EM16 340 1100 F EM16 340 1500 F EM16 340 1850 F...

Page 15: ...put single phase L1 L L3 N single three phase L1 L L2 L3 N three phase L1 L2 L3 L2 L3 N T1 Inverter output connect to U V W terminals of motor T2 T3 P Braking resistor connection terminal Used in appl...

Page 16: ...al Loss Final count value reached Initial count value recahed PLC Status Indicator PLC control 250VAC 1A 30VDC 1A R1B NC Normally closed R1C COMMON R2A R2B 24VPower supply COM Digital signal common te...

Page 17: ...5 1 IP20 dimensions Frame1 IP20 Single phase 230V 0 37 0 75 kW Three phase 400V 0 75 1 5 kW 2 Q1 2 Q2 W1 H1 H W2 W E D D1 Model Dimensions mm N W Kg W W1 W2 H H1 D D1 E Q1 Q2 EM16 123 0037 F 20 90 6 8...

Page 18: ...e 400V 2 2 4 0 kW W1 H1 H2 W2 W 2 Q1 E D1 D D2 2 Q2 H Model Dimensions mm N W Kg W W1 W2 H H1 H2 D D1 D2 E Q1 Q2 EM16 123 0150 F 20 128 7 118 118 187 6 177 6 197 5 150 133 8 141 8 48 2 4 5 4 5 2 5 EM1...

Page 19: ...400V 5 5 11 kW W1 H W D D1 D2 E W2 H2 2 Q1 H1 2 Q2 Model Dimensions mm N W Kg W W1 W2 H H1 H2 D D1 D2 E Q1 Q2 EM16 340 0550 F 20 186 9 175 176 260 9 249 8 273 197 2 184 189 76 7 4 5 4 5 6 7 EM16 340 0...

Page 20: ...me4 IP20 Three phase 400V 15 18 5 kW Model Dimensions mm N W Kg W W1 W2 H H1 H2 D D1 D2 E1 E2 Q1 Q2 EM16 340 1500 F 20 224 6 207 20 436 303 5 330 9 200 7 187 5 192 5 64 192 5 6 6 13 7 EM16 340 1850 F...

Page 21: ...0V 0 37 0 75 kW Three phase 400V 0 75 1 5 kW Model Dimensions mm N W Kg W W1 H H1 H2 D D1 D2 D3 Q1 Q2 Q3 EM16 123 0037 F 66 S 150 8 133 3 248 7 230 2 214 2 183 200 200 49 5 5 4 5 4 10 6 2 9 EM16 123 0...

Page 22: ...1 5 2 2 kW Three phase 400V 2 2 4 kW Model Dimensions mm N W kg W W1 H H1 H2 D D1 D2 D3 Q1 Q2 EM16 123 0150 F 66 S 198 115 335 315 337 9 218 4 235 2 235 2 79 8 7 7 5 98 EM16 123 0220 F 66 S EM16 340...

Page 23: ...IP66 Three phase 400V 5 5 18 5 kW Model Dimensions mm N W kg W W1 H H1 H2 D D1 D2 D3 Q1 Q2 EM16 340 0550 F 66 S 222 8 140 460 440 466 3 246 6 266 5 263 5 96 7 7 12 68 EM16 340 0750 F 66 S EM16 340 11...

Page 24: ...frequency is displayed Variable Resistor FREQ SET Used to set the frequency Keys On Keypad 8 buttons RUN RUN Run at the set frequency STOP STOP Decelerate or Coast to Stop Increment parameter number...

Page 25: ...d setup Group 08 Drive and motor Protection Group 09 Communication function setup Group 10 PID function setup Group 11 Performance control functions Group 12 Digital Display Monitor functions Group 13...

Page 26: ...Keypad 2 External AI1Analog Signal Input 3 External AI2 Analog Signal Input 4 External Up Down Frequency Control 5 Communication Setting Frequency 6 PID Ouput Frequency 7 Pulse Input 6 00 07 Main and...

Page 27: ...lts Hz Curve Modification Torque Boost 0 10 0 0 0 1 01 11 V F start Frequency 0 00 10 00 0 00 Hz 01 12 Slip compensation gain 0 05 10 00 0 10 S 01 13 V F Mode Select 0 Mode 0 1 Mode 1 by models 7 Grou...

Page 28: ...eed Search 20 Energy Saving only V F 21 Reset PID integral value to Zero 22 Counter Input 23 Counter Reset 24 PLC Input 25 Pulse Input Width Measure S3 6 26 Pulse Input Frequenct Measure S3 6 27 Enabl...

Page 29: ...03 13 Preset Frequency Reached Level 0 00 599 00 0 00 Hz 1 03 14 Frequency Reached Detection Range 0 00 30 00 2 00 Hz 1 03 15 Preset output current reached 0 1 15 0 0 1 A 03 16 Preset output Current d...

Page 30: ...egative 0 1 04 05 AI1 Slope 0 Positive 1 Negative 0 1 04 06 AI2 Signal Verification Scan Rate 1 200 50 2ms 04 07 AI2 Gain 0 1000 100 1 04 08 AI2 Bias 0 100 0 1 04 09 AI2 Bias Selection 0 Positive 1 Ne...

Page 31: ...5 Hz 0 00 Hz 1 05 17 Preset Speed0 Acctime 0 1 3600 0 10 0 Sec 1 05 18 Preset Speed0 Dectime 10 0 Sec 1 05 19 Preset Speed1 Acctime 10 0 Sec 1 05 20 Preset Speed1 Dectime 10 0 Sec 1 05 21 Preset Speed...

Page 32: ...Of final step to run Continues to run from the unfinished step if restarted 4 Single cycle Starts a new cycle if restarted 5 Periodic cycle Starts a new cycle if restarted 6 Single cycle then hold th...

Page 33: ...0 0 Sec 06 19 Auto_ Run Mode Running Time Setting 3 0 0 Sec 06 20 Auto_ Run Mode Running Time Setting 4 0 0 Sec 06 21 Auto_ Run Mode Running Time Setting 5 0 0 Sec 06 22 Auto_ Run Mode Running Time Se...

Page 34: ...Direction 9 0 06 42 Auto_ Run Mode Running Direction10 0 06 43 Auto_ Run Mode Running Direction 11 0 06 44 Auto_ Run Mode Running Direction12 0 06 45 Auto_ Run Mode Running Direction13 0 06 46 Auto_...

Page 35: ...Time 0 0 25 0 KEB Deceleration Time 0 0 Sec 07 15 DC Injection Brake Mode 0 Current Mode 1 Voltage Mode 1 6 07 16 DC Injection Brake Level Voltage Mode 0 0 10 0 4 0 6 Group 08 Drive Motor Protection F...

Page 36: ...ion 0 Overload protection Standard Motor 0 1 Overload protection Inverter Duty Motor 08 12 Motor Overload Protection Curve 0 Motor Overload Protection for General loads OL 103 150 for 1 Minutes 0 1 Mo...

Page 37: ...tion to Stop 00 17 Deceleration Time 2 3 Continue Operating 0 09 08 Comm Fault Tolerance Count 1 20 3 09 09 Wait Time of Inverter Transmission 5 65 5 ms Group 10 PID Function Setup No Description Rang...

Page 38: ...Integral value Error Margin Units 1 Unit 1 8192 0 100 0 10 17 PID Sleep Frequency Level 0 00 599 00 0 00 Hz 10 18 PID Sleep Function Delay Time 0 0 25 5 0 0 Sec 10 19 PID Wake up frequency Level 0 00...

Page 39: ...onitor Functions No Description Range Factory Setting Unit Note 12 00 Extended Display Mode 00000 88888 Each digit can be set from 0 to 8 as listed below 00000 1 0 Default Display Frequency and Parame...

Page 40: ...trol Circuit Capacitors is Invalid xxx1x Life Alarm of Control Circuit Capacitors is Valid xx0xx Life Alarm of Main Circuit Capacitors is Invalid xx1xx Life Alarm of Main Circuit Capacitors is Valid 1...

Page 41: ...Enable all Functions 1 Preset Speeds from 05 01 to 05 15 Can t be Changed 2 All Functions Can t be Changed Except for Preset speeds from 05 01 to 05 15 3 Disable All Functions Except 13 06 0 13 07 Par...

Page 42: ...14 20 Setting Value1 of C5 0 65535 0 14 21 Setting Value1 of C6 0 65535 0 14 22 Setting Value1 of C7 0 65535 0 14 23 Setting Value1 of C8 0 65535 0 14 24 Setting Value1 of AS1 0 65535 0 14 25 Setting...

Page 43: ...alue of T7 0 9999 0 15 13 Current Value of T7 mode 7 0 9999 0 15 14 Current Value of T8 0 9999 0 15 15 Current Value of T8 mode 7 0 9999 0 15 16 Current Value of C1 0 65535 0 15 17 Current Value of C2...

Page 44: ...o result then replace the inverter EPr EEPROM problem Faulty EEPROM Consult with the supplier COt Communication error Communication disruption Check the wiring CtEr Current Sensor detection error Curr...

Page 45: ...cation LF Output phase loss Loss of output voltage on any of the phases 1 Check output cable connection 2 Determine resistance between the lines 3 Check whether the terminals are loose Faults which ca...

Page 46: ...00 Err1 Keypad operation error 1 Press or while 00 05 00 06 0 or running at preset speed 2 Attempt to modify the Parameter Can not be modified during operation refer to the parameter list 1 The or is...

Page 47: ...se and re activate the run contact to restart the inverter E S External Rapid stop When external rapid stop input is activated the inverter will decelerate to stop and the display will flash with E S...

Page 48: ...y excessively 1 Minimize the variation of the load 2 Consider increasing the capacities of the inverter and the motor Is the input power erratic or is there a phase loss 1 Consider adding an AC reacto...

Reviews: