VMX-agility Series Quick Start Guide
MAN-AGY-014. Version 01 28/05/2019
VMX-AGY-301
–
305 have permanently fitted fans
General Specification (continued)
Electronic
overload relay
with manual reset and
thermal memory
Trip Class
10 (factory default), 20 or 30 (selectable)
Current setting
See Electronic Overload Relay Current Settings
Rated frequency
50 to 60Hz ± 5Hz
Time-current characteristics
See Fig.1 for trip curves (Trip time T
p
± 20%)
1)
With optional VMX-AGY-020 or VMX-AGY-021 power supply module.
2)
Must be supplied by class 2, limited voltage current or protected by a 4A UL 248 listed fuse.
3)
Compliant with Annex S of IEC 60947-1:2007 at 24Vdc
4)
Not applicable for UL.
5)
The safety functions were not evaluated by UL. Listing is accomplished according to requirements of Standard UL 508 and CSA14-13, general use
applications
6)
For models VMX-AGY-101 to VMX-AGY-209 the main circuit IP20 rating only applies when the finger guards as supplied are fitted.
7)
Transient surge suppression shall be installed on the line side of this equipment and shall be rated 600_V (phase to phase), suitable for overvoltage
category III, and shall provide protection for a rated impulse withstand voltage peak of 6 kV.
Electromagnetic Compatibility
EMC Emission levels
EN 55011
Class A
1
EMC Immunity levels
IEC 61000-4-2
8kV/air discharge or 4kV/contact discharge
IEC 61000-4-3
10 V/m
IEC 61000-4-4
2kV/5kHz (main and power ports)
1kV/5kHz (signal ports)
IEC 61000-4-5
2kV line-to-ground
1kV line-to-line
IEC 61000-4-6
10V
1 NOTICE: This product has been designed for environment A. Use of this product in environment B may cause
unwanted electromagnetic disturbances, in which case the user may be required to take adequate mitigation
measures
Fan Option
VMX-Agility model
Maximum duty cycle F-S with optional fan fitted
VMX-AGY-101 to VMX-AGY-203
90-40 (40 cycles per hour)
VMX-AGY-205
90-30 (30 cycles per hour)
VMX-AGY-207
90-20 (20 cycles per hour)
VMX-AGY-209
90-10 (10 cycles per hour)
Technical Information/Specification