Version 1.5
© Openpath 2021
5
MOUNTING INSTRUCTIONS
The SDC can be mounted a few different ways: on a single or double gang box or on
drywall.
To install on a standard US 1-gang box:
1. Use two 6-32 screws (A) to attach backplate (B) to gang box
2.
Recommended:
Use the provided drywall screws (C) and anchors (not shown)
on drywall for added stability
3. Snap on main housing (D) to backplate (B)
4. On the right side of the main housing (D), ensure that the two edge clips fit into
their respective notches on the backplate (B)
5. Press firmly on the main housing (D) to snap into place
6. Partially unscrew pre-installed M4 set screw (E) to secure main housing (D) to
backplate (B)
7. Use the cable slot (F) to hold cables while wiring; see
8. Snap on front cover (G)
Note:
For a double gang box, follow the directions above, using additional 6-32
screws.
Figure 1 Mounting SDC to wall
1. Use the provided drywall screws (C) and anchors (not shown) to attach
backplate (B) to wall