TROUBLESHOOTING 
 

SYMPTOM 

LIGHT 

PATTERN 

SOLUTION 

No lights are on -  

the unit seems 

completely dead 

N/A 

Verify L1, L2 & L3 are connected to terminals 3, 4 & 5. 
Measure the three line-to-line voltages. If any of the 
voltages are below the specified operating voltage, the 
MotorSaver

®

 does not have enough power to operate 

its internal electronics. If the voltages are correct, call 
SymCom at (800) 843-8848 or (605) 348-5580. 

Red light is blinking  

(on initial power-up) 

 

 

RED 

Turn off the 3-phase power. Swap any two leads 
powering the MotorSaver

®

 (L1, L2, or L3). There is a 

50-50 chance of connecting L1, L2 and L3 correctly the 
first time. Reapply 3-phase power. 

Red light is blinking 

(after the motor has 

been running) 

 

 

RED 

The incoming lines have been reverse-phased. The 
MotorSaver

®

 is preventing the motor from running 

backwards. Correct the phase sequence. 

Red light is blinking 

in this pattern 

 

 

RED 

The voltage is unbalanced or single-phased. Measure 
the incoming line voltages and calculate the % 
unbalance according to the procedure outlined earlier 
in this document. If the voltage unbalance does not 
exceed the % unbalance reset value, call SymCom at 
(800) 843-8848 or (605) 348-5580. 

Red light is blinking 

in this pattern 

 

RED 

The voltage is high. Measure the three line-to-line 
voltages. Calculate the average according to the NEMA 
unbalance formula.  If the average voltage is 7% above 
the nominal voltage as selected by the LINE VOLTAGE 
ADJUST setting, the MotorSaver

® 

is functioning 

properly. If the voltage is within 7%, call SymCom at 
(800) 843-8848 or (605) 348-5580. 

Red light is on 

steady 

RED 

The voltage is low. Measure the three line-to-line 
voltages.  Calculate the average according to the 
NEMA unbalance formula.  If the average voltage is 7% 
below the nominal voltage as selected by the LINE 
VOLTAGE ADJUST setting, the MotorSaver

® 

is 

functioning properly. If the voltage is within 7%, call 
SymCom at (800) 843-8848 or (605) 348-5580.  

Green light blinks 

and motor is not 

running 

 

GREEN 

The MotorSaver

®

 is timing through the restart delay 

and will energize its contacts when finished, or the 
MotorSaver

®

 is in manual reset mode and requires a 

manual reset to energize its contacts. 

Green light is on 

steady, but motor 

does not start 

GREEN 

The MotorSaver

®

 is in run mode. Ensure other control 

devices are allowing the motor to start. Check control 
circuit for loose wires or malfunctioning switches. 

 
 

 

© 2010 SymCom, Inc. All Rights Reserved                                                                                        7  

Summary of Contents for 201-575-AU

Page 1: ...INSTALLATION INSTRUCTIONS 2880 North Plaza Drive Rapid City South Dakota 57702 800 843 8848 605 348 5580 fax 605 348 5685 MODELS 201A AU 201 575 AU Revision B1 Rapid City SD USA 02 2010 II_201A AU_B1...

Page 2: ...r the motor control panel If the location is wet or dusty the MotorSaver should be mounted in a NEMA 4 or 12 enclosure 2 Mount an 8 pin socket to the motor control back panel SymCom P N OT08 PC sold s...

Page 3: ...Figure 1 Typical Wiring Diagram for Control and Alarm Figure 2 Pin Out Diagram 2010 SymCom Inc All Rights Reserved 3...

Page 4: ...tart delay is typically set between 10 and 20 seconds Trip Delay Rotate the TRIP DELAY SEC knob to the desired setting This setting does not affect the trip delay on single phasing faults See SPECIFIC...

Page 5: ...rage Example The measured line to line voltages are 203 210 and 212 Average 203 210 212 208 3 3 The maximum deviation from the average is the largest difference between the average voltage 208 3 and a...

Page 6: ...When the MotorSaver trips on a fault the red STATUS light will display the fault code until the condition clears and the unit is reset by turning the RESTART SEC knob away from the M position until th...

Page 7: ...e reset value call SymCom at 800 843 8848 or 605 348 5580 Red light is blinking in this pattern RED The voltage is high Measure the three line to line voltages Calculate the average according to the N...

Page 8: ...3 15 80 01 5 12 7 NOTE Use of the OT08 PC or RB08 PC octal socket manufactured by Custom Connector Corp is required for the MotorSaver to qualify as a UL Listed device The OT08 PC is 35mm DIN rail co...

Page 9: ...ndensing per IEC 68 2 3 Maximum Input Power 5 W Standards Passed Electrostatic Discharge ESD IEC 61000 4 2 Level 3 6kV contact 8kV air Radio Frequency Immunity Radiated 150 MHz 10V m Fast Transient Bu...

Page 10: ...2010 SymCom Inc All Rights Reserved 10 NOTES...

Page 11: ...2010 SymCom Inc All Rights Reserved 11 NOTES...

Page 12: ...se see Terms and Conditions at www symcom com Visit us at www symcom com to see our complete product listing Need something special Contact SymCom today for your custom solution 800 843 8848 2010 SymC...

Reviews: