5.2 Installation site selection
The following must be considered when selecting the location for an inverter:
The mounting and installation method must be appropriate for the inverter
and dimensions. Mount on a solid surface.
The environment temperature
inverter(-25
℃
to +60
℃
; derating between 45
Do not install the inverter at altitude of above 2000m, otherwise the inverter will
derate.
Do not install the inverter in corrosive gas or
Do not install the inverter in an area with risk of flood or frozen.
Do not install the inverter in confined space or high humidity.
Do not expose the inverter to strong cold air, steam, fog or water.
Do not install the inverter closed
The inverter must be installed vertically or with a backward tilt of no more than 15
degrees.
The connection area must face downwards.
•
Mount the inverter at eye level. Given the weight of the device, this will facilitate
disassembly if service work is necessary.
•
The ambient temperature should be
performance.
•
Do not expose the inverter to direc
thus power reduction.
•
In living areas, do not mount the unit on plasterboard walls or similar in order to avoid
audible vibrations. When in use, the inverter emits noises which may be perceived as a
nuisance in a living area.
•
Observe the recommended clearances to walls
shown in the diagram. This ensures adequate heat
the optional DC switch.
•
If multiple inverters are mounted in
the clearances between the inverters and ensure an adequate
The Solar Family Series Inverter
17
Installation site selection
The following must be considered when selecting the location for an inverter:
The mounting and installation method must be appropriate for the inverter
Mount on a solid surface.
temperature should not exceed the working temperature of the
; derating between 45
℃
to 60
℃
)
Do not install the inverter at altitude of above 2000m, otherwise the inverter will
Do not install the inverter in corrosive gas or dip in liquid such as sea water.
Do not install the inverter in an area with risk of flood or frozen.
Do not install the inverter in confined space or high humidity.
Do not expose the inverter to strong cold air, steam, fog or water.
Do not install the inverter closed to TV cable or antenna cable.
The inverter must be installed vertically or with a backward tilt of no more than 15
The connection area must face downwards.
Figure 17
Mount the inverter at eye level. Given the weight of the device, this will facilitate
service work is necessary.
The ambient temperature should be lower than 40
°
C to achieve optimal
Do not expose the inverter to direct sunlight as this can cause excessive heating and
In living areas, do not mount the unit on plasterboard walls or similar in order to avoid
vibrations. When in use, the inverter emits noises which may be perceived as a
Observe the recommended clearances to walls ,other inverters or other objects, as
diagram. This ensures adequate heat sink and sufficient room to operate
If multiple inverters are mounted in areas with high ambient temperatures, increase
between the inverters and ensure an adequate fresh-air supply. This will
The Solar Family Series Inverter
The following must be considered when selecting the location for an inverter:
The mounting and installation method must be appropriate for the inverter’s weight
should not exceed the working temperature of the
Do not install the inverter at altitude of above 2000m, otherwise the inverter will
such as sea water.
The inverter must be installed vertically or with a backward tilt of no more than 15
Mount the inverter at eye level. Given the weight of the device, this will facilitate
achieve optimal
as this can cause excessive heating and
In living areas, do not mount the unit on plasterboard walls or similar in order to avoid
vibrations. When in use, the inverter emits noises which may be perceived as a
,other inverters or other objects, as
and sufficient room to operate
ambient temperatures, increase
air supply. This will