START AND STOP
NOTE
!
CAUTION
!
MACHINE WITH EMERGENCY BUTTON
Pressing the button the engine will stop
immediately in any working condition.
CAUTION
!
The starting of the unit can be effected in 2 different
modes:
1) Start with EP6 key (Engine Control)
Put the “SWITCH BOARD” selector on ON. Turn
the key on “ON”, the EP6 display shows only on
the machines with mounted glow plugs for 5 secs,
the symbol “UUUU”, then the message “Sta”
appears the engine can be started, for which turn
the key on “start” and start the engine.
On the display the word “Sta” remains for about
20 secs then automatically disappears; the engine
must be
started within 20 secs, otherwise the
EP6 blocks the starting and on the display the
word “fail” appears. Turning the key on “OFF” the
EP6 is reset and a new starting cycle can be
fixed.
Stop
:
it is COMPULSORY to disconnect the load first,
then to stop the engine turn the key on “OFF”.
2)
Remote starting with TCM35
Put the “SWITCH BOARD” selector on ON.
Connect TCM35 to the plug on the front panel
and put the switch on “0”.
Turn the key on ON in the EP6 (Engine Control),
wait for the various signals to go out then press
the button “AUTO” in the EP6 until the led “AUTO”
flashes.
Shift the switch on “I” in the TCM35 and
automatically the starting cycle will start. On the
machines with mounted glow plugs appears in
the display EP6 (for about 5 secs), the symbol
“UUUU“; the starting cycle includes 3 starting
trials.
When the engine starts the led “AUTO” remains
lit continuously and simultaneously the red warning
light will light in the TCM35.
Stop:
it is COMPULSORY to disconnect the load first,
then shift the switch of the TCM35 on “0”, the
engine will stop immediately.
Turn clockwise to reset the button.
For safety reason the key must be kept by
qualified personel.
NOTE
!
Do not alter the primary conditions of regulation
and do not touch the sealed parts.
Check daily
RUNNING-IN
During the first 50 hours of operation, do not use
more than 60% of the maximum output power of
the unit and check the oil level frequently, in any
case please stick to the rules given in the engine
use manual.