PROTECTIONS

INSULATION MONITORING

M

39.10

REV..0-05/01

USE AS TROUBLE INDICATOR:

Placed on the front panel, the insulation monitor (A3) 

is a relay which controls continuously the insulation 

of the generation a.c. circuits towards the ground.

The device generates internally a continuous 12V 

voltage which is applied between the circuit under 

control and the ground.

USE AS TROUBLE INDICATOR AND INTERVEN-

TION:

The insulation monitor controls a device (release 

coil, contactor, etc.) which opens the whole circuit, 

lifting voltage in the whole part of the machine a.c. 

generation.

USE OF RI – R22M MODEL:

-  To vary the regulation call our Technical Assist-

ance Department

- The LED ON shows that the device is fed.

- Check that it works correctly pressing the TEST 

push button

-  The  LED  TRIP  will  simulate  on  intervention  or 

anyway will show the real intervention in case the 

insulation fails.

-  Reset the circuit pressing the RESET  push button 

after having checked the plant and removed the 

problem cause.

Don not intervene on the setting of the protection 

switch. Before using the machine check the ON 

warning lamp lighting.

NOTE

!

LEGEND:

A3.1  -   Adjustment  potentiometer  insulation  resi-

stance

A3.2  -   Manual reset push button

A3.3  -   Test push button

A3.4  -   Auxiliary fedding presence LED

A3.5  -   TRIP LED

A3.2

A3.3

A3.1

A3.5

A3.4

RESET

TEST

ON TRIP

25

50

75

100

k ohm

USE OF SRI/D3 MODEL

-  To vary the regulation call our Technical Assist-

ance Department

-  The  warning  light  ON  shows  that  the  device  is 

fed.-

-  Pressing  a  long  time  the  Test  push-button,  the 

Fault led lights and the Alarm led twinkles;

-  Leaving it, the Alarm led goes off while the Fault 

led remains lit. The pressure on the Reset key 

brings the device back to initial conditions.

-  If  the  insulation  resistance  goes  down  below 

the fixed alarm value, the Alarm led twinkles, at 

the same time the Alarm contact switches; if the 

insulation  resistance  goes  down  furtherly  and 

becomes inferior to the fixed value for the Fault, 

the Fault led lights  and at the same time both ex-

change contacts switch putting the Fault in activity 

and the Alarm at rest.

-  After  having  checked  the  device  and  removed 

the cause of the problem, re-establish the circuit 

pressing the push-button RESET.

LEGEND:

D1  Regulation of Alarm threshold

D2  Regulation of Fault threshold

D3  Led, fault indication

D4  Led feeding indication

D5  Led Alarm indication

D6  Test push-button

D7  Reset push-button

25/05/01  M39GB

Summary of Contents for GE 20 YSX

Page 1: ...USE AND MAINTENANCE MANUAL MOSA 25 09 12 84920M00 preparato da UPT approvato da DITE GE 20 YSX 849209003 GB 0 3 1 3...

Page 2: ...des a tank an engine alternator unit fixed on the base by elastic dampers a roll bar with hook for an easy and sure lifting a chest hinged to the roll bar for a quick access to the engine and to the a...

Page 3: ...continue to satisfy the needs of its clients aswell as to improve the transparency and thecom munications regarding all the company s activesin accordance with the official procedures and inhar mony w...

Page 4: ...INSTALLATION M 2 7 INSTALLATION AND DIMENSIONS M 3 UNPACKING M 4 2 TRANSPORT AND HANDLING M 6 20 CTL 20 ASSEMBLY M 20 SET UP FOR OPERATION M 21 START AND STOP M 31 CONTROLS M 32 CONTROLS M 39 12 EP6...

Page 5: ...matter In no case MOSA division of B C S S p A will be held responsible for any damaga direct or indirect in relation with the use of the given information MOSA division of B C S S p A does not take...

Page 6: ...mpness and heat You must take into account that some figures contained in it want only to identify the described parts and therefore might not correspond to the machine in your possession INFORMATION...

Page 7: ...elf the list of these directives is part of the declaration of conformity included in any machine standard equipment Here below the adopted symbol CE marking is clearly readable and unerasable and it...

Page 8: ...mber ______________________________ conforme con quanto previsto dalle Direttive Comunitarie e relative modifiche est en conformit avec ce qui est pr vu par les Directives Communautaires et relatives...

Page 9: ...wer PRP maximum available power for use at variable loads for a yearly illimited number of hours The average power to be taken during a period of 24 h must not be over 80 of the PRP It s admitted over...

Page 10: ...persons or things Do not use without protective devices provided Removing or disabling protective devices on the machine is prohibited Do not use the machine if it is not in good technical condition...

Page 11: ...ersons Use only with safety clothing It is compulsory to use the personal protection means given in equip ment Use only with safety clothing It is compulsory to use the personal protection means given...

Page 12: ...tely Wipe up spilled fuel before starting engine An electric shock can kill Shut off fuel of tank when moving machine where it is assembled Avoid spilling fuel on hot engine Sparks may cause the explo...

Page 13: ...s are equipped with a control system that is NOT influenced by standard environmental fac tors and is able to stop the unit in case of anomalous values in the fundamental parameters In order to avoid...

Page 14: ...nce no specific mea sures are needed in this regard In case of doubts concerning your genset do not hesitate to contact our technical sales office Installation instructions M 2 6 1 REV 0 06 10 ATTENTI...

Page 15: ...fix the genset to it by using screw anchors or rag bolts Base dimensions should exceed genset dimensions of at least 200 mm on each side Base should weigh three times static genset weight indicated on...

Page 16: ...duct should be evaluated If the duct is not appropriately insulated room temperature may in crease considerably for this reason it may be necessary to install an electro ventilator for correct air ex...

Page 17: ...Installazione Installation Installation Luftzirkulation Instalaci n GE 20 YSX M 2 7 REV 0 09 12 27 09 12 84920 I...

Page 18: ...Dimensioni Dimensions Dimensions Abmessungen Dimensiones GE 20 YSX M 2 7 1 REV 0 09 12 27 09 12 84920 I...

Page 19: ...rough handling or taking away of parts contained inside the packing or in the set In case you find damages rough handling or absence of parts envelopes manuals etc we advise you to inform immediately...

Page 20: ...ide the panel and to the instruments on the front To access the hook points on the top of the unit use approved ladders only or support from another opera tor climb the ladder using non skid shoes ATT...

Page 21: ...nnected to the generating set baseframe it can not be towed on public roads Therefore it can only be used on private roads and no through traffic zones The maximum speed allowed is 40 km h on smooth s...

Page 22: ...the machine to the ground and place the parking foot definitively regulating at the suitable height ATTENTION Do not substitute the original tires with other types 7 8 9 Nota Lift the machine and asse...

Page 23: ...he state of the battery from the colour of the warning light which is in the upper part Green colour battery OK Black colour battery to be recharged White colour battery to be replaced DO NOT OPEN THE...

Page 24: ...t an easy job A lack in tacking these precautions would result in the mix of different additives used in different coolants which would originate gelatinous substances capable of obstructing the cooli...

Page 25: ...ng and on the display the word fail appears Turning the key on OFF the EP6 is reset and a new starting cycle can be fixed Stop it is COMPULSORY to disconnect the load first then to stop the engine tur...

Page 26: ...ing light PTO HI B5 Auxiliary current push button C2 Fuel level light C3 E A S PCB C6 Control unit for generating sets QEA D Ground fault interrupter 30 mA D1 Engine control unit and economiser EP1 D2...

Page 27: ...Comandi Controls Commandes Mandos GE 20 YSX M 31...

Page 28: ...ol tage operation messages 15 A C socket AUX sockets for load connection I6 Start Local Remote selector Selection of engine control in use Local start control on board EP6 operated Remote start extern...

Page 29: ...0 In case of an Automatic Periodic Test A P T the display will show the message tESt 2 2 MANUAL operating mode To start the engine follow the instructions A Turn ON the KEY SWITCH the EP6 illuminates...

Page 30: ...matically anytime the key switch is turned ON The LEDs and DISPLAY light up for about 1 second 6 0 Parameters and settings The unit is programmed by the supplier of the Gen erating Set Contact the Gen...

Page 31: ...ing for at least 2 seconds the EP6 will energize the over voltage protection Hi U see section 4 0 to stop the engine The inh code inhibits the over voltage P 8 Generator Under Frequency Inh inh 1 to 9...

Page 32: ...P 24 P 24 Crank OFF Inh Crank Termination setting 100 800 rpm If the speed rises above the setting the EP6 terminates the crank cycle One sec onddelay avoids false termination The code Inh inhibits t...

Page 33: ...rror accumulation and in case your unit is programmed to allowAutomatic Periodic Test we recommend the following procedures disconnect the power supply of the EP6 consult your genset supplier wait for...

Page 34: ...ions and nominal values for voltage frequency power factors cos There are various types of power PRIME POWER PRP STAND BY POWER established by ISO 8528 1 and 3046 1 Norms and their definitions are lis...

Page 35: ...e motor allows it see to a start up with reduced voltage star point triangle start up or with autotransformer or use a soft start system In all cases when the user circuit requires the start up of an...

Page 36: ...tection forcefully pressed to prevent its intervention ATTENTION USAGE WITH EAS AUTOMATIC START UP PANEL The electricity generating group in combination with the EAS automatic start up panel forms a u...

Page 37: ...ng NOTE LEGEND A3 1 Adjustment potentiometer insulation resi stance A3 2 Manual reset push button A3 3 Test push button A3 4 Auxiliary fedding presence LED A3 5 TRIP LED A3 2 A3 3 A3 1 A3 5 A3 4 RESET...

Page 38: ...e front plate X1 and or rear plate with a multiple connector N B The remote control TCM 35 can be used only with machines equipped with control and protection device EP6 U7 For use of TCM 35 see page...

Page 39: ...ernal tank at the same level of the generator the minimum diameter of the connecting hoses must be 15 mm the maximum length of the connecting hoses must be 5m A pressure sensor on the return pipe of t...

Page 40: ...s and connections daily Clean periodically using a vacuum cleaner DO NOT USE COMPRESSED AIR DECALS AND LABELS All warning and decals should be checked once a year and replaced if missing or unreadable...

Page 41: ...year even if the requested number of hours has not been attained EVERY WEEK EVERY MONTH AND OR AFTER INTERVENTION ON LOAD EVERY YEAR 1 TEST orAUTOMATIC TEST cycle to keep the generating set constantl...

Page 42: ...e Department Black smoke 1 Air filter clogged 2 Overload 3 Injectors defective Injection pump requires calibration 1 Clean or replace 2 Check the load connected and diminish 3 Ask for intervention of...

Page 43: ...motor running speed 2 Voltage regulating device where it is assembled defective or requires calibration 3 Alternator defective 1 Regulate speed to its nominal no load value 2 Adjust regulator device...

Page 44: ...he covers and all the other parts of the machine carefully Protect the machine with a plastic hood and store it in o dry place DIESEL ENGINE For short periods of time it is advisable about every 10 da...

Page 45: ...f the various components of the machine must be made accordingly to rules in force of law a o local rules Particular attention must be paid when getting rid of lubricating oils battery electrolyte and...

Page 46: ...filter clogging T4 Warning light air filter clogging U4 Polarity inverter remote control V4 Polarity inverter switch Z4 Transformer 230 48V W4 Diode bridge polarity change X4 Base current diode bridge...

Page 47: ...GE 15 YSX GE 20 YSX M 61 REV 0 09 12 Schema elettrico Electric diagram Schemas electriques Stromlaufplan Esquema el ctrico 27 09 12 84910 I...

Page 48: ...o di n Pag n 4 Date Appr Approved Project Denomination Machine Modification Date Da Pag Alla Pag To Page From Page Designer of n Desi Dis n Exp Page n Dwg n Disegnatore 5 5 4 3 27 26 3 4 26 27 3 27 4...

Page 49: ...GE 20 YSX M 61 3 REV 0 09 12 Schema elettrico Electric diagram Schemas electriques I GB F D E NL Stromlaufplan Esquema el ctrico 27 09 12 84920 I...

Page 50: ......

Reviews: