INSTALLATION
2.4.2
DIP Switch Confi guration Options
DIP Switches control the operational functions of the inverter as follows.
The default position for these switches is OFF.
Table 1: DIP Switch Confi guration
DIP
Switch
Function
Status
Control Content
1
Operational
Control
OFF
AC Output is controlled by the Remote ON/OFF Switch
ON
AC Output is controlled by the communication command (digital command).
2
Alarm Sounds
OFF
Beeper OFF
ON
Beeper ON
3
Not Used
OFF
Not Used - Default is OFF
ON
Not Used - Default is OFF
4
Low Voltage
Disconnect
OFF
CUSTOM. LVD is set according to the factory default values and the non-default
values can be modifi ed through RS485 communication port or Bluetooth App.
ON
PRESETS. LVD is set with the #5 DIP Switch values and cannot be modifi ed.
5
Low Voltage
Disconnect
PRESETS
(I.E., Default)
For 12 V
(24 V or 48 V)
Systems
OFF
• Alarms when
DC Input
voltage is 10.8 V, (21.6 V or 44.4 V)
• Disconnects
AC Output
when
DC Input
voltage is 10.5 V (21.0 V or 42.0 V),
and
• Restarts
AC Output
when
DC Input
voltage is 11.6 V (25.2 V or 46.4 V)
ON
• Alarms when
DC Input
voltage is 11.8 V (23.6 V or 48.4 V),
• Disconnects
AC Output
when
DC Input
voltage is 11.5 V (23.0 or 46 V), and
• Restarts
AC OUTPUT
when
DC Input
voltage is 12.6 V (25.2 V or 50.4 V).
6
Standby Mode
OFF
AC Output is always ON
ON
AC Output is OFF unless a load > 8 W is detected
7
Not Used
OFF
Not Used - Default is OFF
ON
Not Used - Default is OFF
8
Bluetooth
Communication
OFF
Bluetooth Disabled
ON
Bluetooth Enabled
Figure 11: DIP Switch Confi gurations