TRZ
7.
Highlight TEMP and push the right arrow to
display the temperature. Press ENTER to
return to the Sensor Trim menu.
8.
Highlight OFFS and push the right arrow to
change the offset. Input the desired offset and
push ENTER to return to the Sensor Trim
menu.
9.
Highlight FACTORY TRIM and push the right
arrow to reset the TRZ to the factory settings.
If you do not want to reset the TRZ, skip to step
10.
Note:
Once the factory trim process is
complete, all other trim values are
erased.
Reset takes 5 seconds. Pushing Abort
during this time stops the process.
10. Push HOME to return to the Main Menu.
Displaying the Minimum and Maximum
Process Values
The highest and lowest process values since the last
reset are displayed in the “Data Logger” menu. These
values are held in volatile memory and are irretriev-
able if the TRZ loses power or is reset.
To display the minimum and maximum values:
1.
Highlight DATA LOGGER in the Main Menu
and push the right arrow.
2.
Next to MAX VALUE is the highest process
value since the last reset. Push EXIT to return
to the Data Logger menu.
3.
Next to MIN VALUE is the lowest process value
since the last reset. Push EXIT to return to the
Data Logger menu.
4.
Push HOME to return to the Main Menu.
Resetting the Minimum and Maximum
Process Values
The minimum and maximum process values can be
reset in this menu. Once reset, they are irretrievable.
Resetting the minimum and maximum process values:
1.
Highlight DATA LOGGER in the Main Menu
and push the right arrow.
2.
Highlight RESET MIN/MAX and push the right
arrow to reset the maximum and minimum
process values.
Note:
Reset takes five seconds. Pushing Abort
during this time stops the process.
3.
Push HOME to return to the Main Menu.