SDY

18   The Interface Solution Experts

PC-Programmable Signal 

Isolator/Converter with Display

Installation in  

Hazardous Locations

This section contains important information regarding 

installation of SDY in Hazardous Area Locations.

WARNING: 

 

Substitution of components is not allowed, as it 

may impair the intrinsic safety.

WARNING: 

 

To prevent ignition of flammable or combustible 

atmospheres, disconnect power before servicing.

WARNING: 

 

Explosion Hazard.  Do not disconnect equipment 

when a flammable or combustible atmosphere is 

present.

Maximum operating parameters of the “COM” port 

for use in Non-Hazardous areas shall not exceed 

3.0V, 300mA and 240mW.

 

Specific Conditions of Use

The following instructions must be adhered to 

when the SDY is used in hazardous locations and 

potentially explosive atmospheres.

cFMus Installations

Intrinsically Safe Applications 

Class I, Division 1, Groups A-D 

Class1, Zone 0, AEx ia IIC, Ex ia IIC 

The SDY shall be installed in an enclosure which 

maintains an ingress protection rating of at least 

IP20 and also meets the requirements of ANSI/ISA 

61010-1 or C22.2 No 1010-1.

The COM port shall not be used in Hazardous 

areas.

Nonincendive, Type n Applications  

Class I, Division 2, Groups A-D 

Class1, Zone 2, AEx nA IIC, Ex nA IIC 

When installed as Division 2 equipment, the SDY 

shall be mounted within a tool-secured enclosure 

which meets the requirements of ANSI/ISA 61010-

1or C22.2 No. 1010-1 and be capable of accepting 

the applicable wiring method per the NEC or as 

specified in the C22.1 Canadian Electrical Code, 

Part I. 

When installed as Zone 2 equipment, the SDY shall 

be mounted within a tool-secured enclosure which 

meets the requirements of ANSI/ISA 60079-0 or 

CAN/CSA-E60079-0 and ANSI/ISA 60079-15 or 

CAN/CSA 60079-15 and be capable of accepting 

the applicable wiring methods per the NEC or as 

specified in the C22.1 Canadian Electrical Code, 

Part I.  The enclosure shall, at a minimum, meet the 

requirements of IP54.

On installation of Zone 2 equipment, the SDY 

shall be provided with supply transient protection 

external to the apparatus such that the voltage at 

the supply terminals of the SDY does not exceed 

58.8V peak or 58.8Vdc.

The COM port shall not be used in Hazardous 

areas.

European Union Installations  

(ATEX 2014/34/EU Directive)

Intrinsically Safe Applications - Zone 0 

II 1 G Ex ia IIC 

The SDY shall be installed in an enclosure which 

maintains an ingress protection rating of at least 

IP20.  

 

 

The communications port shall be programmed 

through Moore Industries Cable, Part No. 

 

804-030-26, as described on Control Drawing 

 

100-100-54.

 The Cable cannot be used in Hazardous Areas or 

in ambient temperatures in excess of 75° C.

 

Summary of Contents for SDY

Page 1: ...a n d M o o r e R e l i a b i l i t y All product names are registered trademarks of their respective companies User s Manual SDY PC Programmable Signal Isolator Converter with Display No 235 770 00G...

Page 2: ...tion File from an SDY 10 Setting Output Damping 10 Trimming SDY Output 10 Scaling the SDY Output 11 Setting the Display 11 Trimming the Input 12 Creating a Custom Linearization Table 12 Installation 1...

Page 3: ...ile 2 wire loop powered PC Programmable Signal Isolator Converter that accepts current or voltage input and provides an isolated proportional 4 20mA output See Figure 1 for a list of accommodated inpu...

Page 4: ...asured across 250 resistor Power Supply Effect 0 002 of span per 1V change Over Voltage Performance Continued Protection 48V maximum on output 48V reverse polarity protection on output Maximum Input O...

Page 5: ...DN mounting will fit the TS 32 DIN rail and the TS 35 DIN rail FL Mounting flanges on HP suitable for relay track or screw mounting FLD Mounting flanges on HP suitable for 3 relay track mounting A suf...

Page 6: ...nit tagging input type and range settings and output zero span trim Prior to shipment our team of skilled technicians subjects every SDY to rigorous testing Every product Moore Industries manufactures...

Page 7: ...26 CAUTION MOORE INDUSTRIES ISOLATING CABLE PROVIDES A GALVANIC BARRIER BETWEEN THE TRANSMITTER AND THE PC CONFIGURING IT IT IS NOT NECESSARY TO USE AN ISOLATING CABLE BUT FAILURE TO DO SO MAY RESULT...

Page 8: ...tion of the screen will be blank and the Communication indicator will show steady ON as opposed to blinking During setup the SDY tests the availability of COM Ports 1 through 4 in your system The firs...

Page 9: ...DY Saving the SDY Configuration File to Disk This is an optional procedure You do not have to save the file to disk in order to download the file into SDY memory Use this procedure to save information...

Page 10: ...e box to the right of the Damping sec area and type in a number between 0 and 20 032 This number is the number of seconds that the sensor s value will be averaged over Trimming SDY Output The SDY has...

Page 11: ...u in Figure 4 and the radio button on Figure 5 both have Input selected then Display Zero will match Input Zero and Display Full will match Input Full Figure 5 Use the Display radio button to switch f...

Page 12: ...the table fields to set values for input and output from the transmitter s intended application Use the Up Down Left and Right arrow keys on the PC keyboard to move the cursor among the cells in the t...

Page 13: ...points but the first and last points in the curve always default to the 0 and 100 input scale input range If you decide not to use all 85 points you must change the number of points in the Points fie...

Page 14: ...Ground Wiring Practices Moore Industries recommends the following ground wiring practices Any Moore Industries product in a metal case or housing should be grounded The protective earth conductor must...

Page 15: ...Display Figure 12 Connecting the HP Housed SDY PS PS 1 2 3 4 SDY 10 278 MA 10 42Vdc POWER SOURCE CURRENT METER CALIBRATED 0 50mA CURRENT SOURCE I I CALIBRATED 0 10V VOLTAGE SOURCE V V PS PS 1 2 3 4 SD...

Page 16: ...ions of the explosion proof BH housing for the SDY unit 84mm 3 30 in 118mm 4 65 in 130 mm 5 12 in 112mm 4 40 in 82 6 mm 3 25 in 64mm 2 50 in INSTRUMENT TAG 116 mm 4 56 in 27mm 1 05 in CONDUIT FITTING...

Page 17: ...le Signal Isolator Converter with Display FRONT VIEW SIDE VIEW 61mm 2 4 in 83mm 3 25 in 62mm 2 45 in 64mm 2 50 in 66mm 2 58 in 76mm 3 00 in 43mm 1 70 in 18mm 70 in PS PS 1 2 3 4 SDY 16 203 MA Figure 1...

Page 18: ...Ex nA IIC Ex nA IIC When installed as Division 2 equipment the SDY shall be mounted within a tool secured enclosure which meets the requirements of ANSI ISA 61010 1or C22 2 No 1010 1 and be capable of...

Page 19: ...ons Zone 0 Ex ia IIC The SDY shall be installed in an enclosure which maintains an ingress protection rating of at least IP20 The communications port shall be programmed through Moore Industries Cable...

Page 20: ...led and supplied with the correct power SDY transmitters begin to operate Depending upon environmental conditions they can be expected to continue to operate unattended for extended periods of time Ma...

Page 21: ...he installation diagram for the SDY carrying the intrinsically safe option It also includes guidelines for setting up zener barriers necessary in these types of applications These diagrams must be use...

Page 22: ...SDY 22 The Interface Solution Experts PC Programmable Signal Isolator Converter with Display...

Page 23: ...SDY The Interface Solution Experts 23 PC Programmable Signal Isolator Converter with Display...

Page 24: ...SDY 24 The Interface Solution Experts PC Programmable Signal Isolator Converter with Display...

Page 25: ...ginal Buyer only and not to Buyer s customers or the users of Buyer s products unless Buyer is an engineering contractor in which case the policy shall extend to Buyer s immediate customer only This p...

Reviews: