System Status Summary
Table 6.4. MODBUS register: 9502
Bit Name
What it Means
What to Do
0
Diagnostic
Failure
One of the diagnostics has detected
a fault
Contact Moore Industries
Customer Support
1
IO Channel
System Error
One or more IO channels are
reporting a system failure
See IO Channel Consolidated
Status Registers
2
IO Channel
General Error
One or more IO channels are
reporting a general failure
See IO Channel Consolidated
Status Registers
3
IO Channel
Warning
One or more IO channels are
reporting a warning
See IO Channel Consolidated
Status Registers
4
User
Configuration
Error
User configuration error
See
User Configuration Error
Register
5
Reserved
6
Reserved
7
Configuration
Storage Error
Error detected in non-volatile
memory storage of configuration
See Configuration Storage Error
Register
8
Internal Error
Indicates an HES internal fault
Contact Moore Industries
Customer Support
9
Security
Status
Indicates open security settings
See System Security Status
User Configuration Error
Table 6.5. MODBUS register: 9513
Bit Name
What it Means
What to Do
0
IO Channel 1
Config Error
IO Channel 1 has a configuration
error
Correct configuration error
1
IO Channel 2
Config Error
IO Channel 2 has a configuration
error
Correct configuration error
2
IO Channel 3
Config Error
IO Channel 3 has a configuration
error
Correct configuration error
3
IO Channel 4
Config Error
IO Channel 4 has a configuration
error
Correct configuration error
4
HART Config
Error
The HART configuration has an error Correct configuration error
5
MODBUS
Config Error
The MODBUS configuration has an
error
Correct configuration error
6
Network
Config Error
The network configuration has an
error
Correct configuration error