Moore Industries-International, Inc.
Table 6.1. LED Indication and device status
LED
Color
Description
Ready
RED
Initializing on power up or Unit Fault
GREEN
System OK
Channel X
RED
Initializing, Fault or No HART
communication
GREEN
Channel OK and HART communication
with all field devices
RED/GREEN
Some, but not all field devices
responding to polling
System Status Registers
The HES has a wealth of diagnostic data to help identify any HES or field device issues. The
status registers are organized in a hierarchy, with the higher levels summarizing the contents of
the lower levels (see table 6.2). These registers are displayed on the ‘System Status Registers’
webpage and can also be found in the MODBUS registers.