MSD Servo Drive DC-AC Operation Manual
20
Id.-No.: CA97554-001 Date: 06/2012
•
Grounding
The grounding measures of relevance to the servo drive are detailed in section 3.4
on page 24.
•
External components
− Place larger consumers near the supply.
− Contactors, relays, solenoid valves (switched inductors) must be wired with
fuses. The wiring must be directly connected to the respective coil.
− Switched inductors should be at least 0.2 m away from process controlled as-
semblies.
If you need more details on installation please contact the Moog Helpline (see page 50).
Step
Action
Comment
1.
Identify the terminal assignment applicable
to your device.
Section 3.2 for Size 1 to Size 4
Section 3.3 for Size 5 and Size 6A
2.
Connecct all required input and output units
to the control terminals and option interfaces
where appropriate.
Section 3.7
3.
Connect the encoder and motor.
4.
Connect the protective conductor and the
supply voltages using the ready made-up
cables (DC Link).
5.
Continue with commissioning ind section 4.