Commissioning
= selected setting/component
Connections
Termi-
nals
Terminal designation
Cable type
Control supply
X9/10
+24 V DC / pin 1 = + , pin 2 = –
Standard
Precharge/mains synchro-
nisation, auxiliary relay
X21
L1/L2/L3 (400/460/480 V
AC
)
HREL
Default
shielded
Mains supply
X12
L1/L2/L3/PE (400/460/480 V
AC
)
Default
shielded
Table 4.1 Voltage supply
Connection
Socket
Designation
Cable type
USB
X2
USB A
CC-USB 03
TCP / IP (Ethernet)
X3
RJ45
CC_ECL 03
Table 4.2 Communication with PC using Moog DriveAdministrator 5 user software
Connection
Termi-
nals
Terminal designation
Cable type
+24 V DC
X4/22
ISDSH
Default
shielded
ENPO (Start)
X4/10
ENPO
Default
shielded
Table 4.3 Communication via terminals
4.2.1
System requirements
y
Installed Power Supply Unit (see section 3, p. 25) Details on initial
commissioning can be found in the following section 4.2.2, p. 52
y
Section 2, "Installation", and section 3, "Starting Moog
D
rive
A
DministrAtor
5", of
the Moog
D
rive
A
DministrAtor
5 Installation Manual worked through
y
Connection between PC and Power Supply Unit (Ethernet or USB)
ATTENTION!
During commissioning strictly comply with the safety regulations specified in
section 1, p. 9.
4.2.2
Wiring of components
1.
For complete wiring all power supply, communication and service connections must be connec-
ted to the appropriate terminals, using the cables and leads provided for this purpose. Ensure
adequate shielding - see section 3.2, p. 25.
DANGER FROM ELECTRICAL TENSION!
Never wire or disconnect electrical connections while they are live. Disconnect
the device from the mains supply (400/460/480 V
AC
) before working on it.
Work on the device only once the DC link voltage has fallen below 50 V
residual voltage (measured at terminals X12/ZK+ and X12/ZK–).
!