Page 9
LDVPV47 Linear Power Vent System
XG0750 -112911
Installation
Section:
Figure 9.
Conduit and Wiring Clearances.
Wiring Installation
Connect the wiring to the linear power vent as outlined in the previ-
ous section, and connect the wiring to the fireplace as outlined in the
schematic below. Ensure that the proper clearances are maintained
for the wiring and conduit.
When installing the wiring it must never run above the vent run
and it must be at least 1" clear of all venting.
1” Clearance
Mounting of Linear Power Vent for
specific Model Fireplaces
L52-DF, and
L52-DF-ST Gas fireplace models.
Figure 8.
L52-DF and L52-DF-ST vent clearances.
4’-0” MIN
Power Vent
1” MIN
4 -0 Clearance / void must be maintained at both ends of Power vent
unit, thru to exterior termination. This clearance does not include wire
conduit, pipe or other neccessary building component. It does however
include fibre insulation, and/or other heat retaining materials.
4’-0” MIN
Figure 7.
LDVPV47 Linear Power Vent Framing in steel studs.
Figure 7a.
LDVPV47 Linear Power Vent Framing to cement roof.
Important:
0” Clearance is required on mounting
surface if LDVPV is Listed under 28,000Btu.
If over 28,000Btu 1” must be maintained or
30% free air space surounding LDVPV.