Page 9
HWDF-Series Gas Fireplace
Part No. XG0190 - 071409
PEL
Available Top Vent Components
The following venting components are available for the
HW38-DF,
Top Vent
:
4" / 7" Venting
5" / 8" Venting
A - Termination
MTO-3 (3" Length)
MTO-3F (3" Length)
PTO-3 (3" Length)
PTO-3F (3" Length)
B - Stucco Kits
MSR (Stucco Frame)
MOSR (Stucco Can)
BSR ( Brick Can)
MSR (Stucco Frame)
MOSR (Stucco Can)
BSR ( Brick Can)
C - Flex Sections
MFL-1 (12" Section)
MFL-2 (24" Section)
MFL-3 (36" Section)
MFL-4 (48" Section)
PFL-1 (12" Section)
PFL-2 (24" Section)
PFL-3 (36" Section)
PFL-4 (48" Section)
D - Rigid
Sections
MEXT-1 (12" m/f Section)
MEXT-2 (24" m/f Section)
MEXT-3 (36" m/f Section)
MEXT-4 (48" m/f Section)
PEXT-1 (12" m/f Section)
PEXT-2 (24" m/f Section)
PEXT-3 (36" m/f Section)
PEXT-4 (48" m/f Section)
E - Elbows
MEL-90MM (m/m 90° Elbow)
MEL-90FF (f/f 90° Elbow)
MEL-90FM (f/m 90° Elbow)
PEL-90MM (m/m 90° Elbow)
PEL-90FF (f/f 90° Elbow)
PEL-90FM (f/m 90° Elbow)
NOTES:
All dimension lengths for vertical or horizontal runs are
measured from centre of the vent pipe.
Venting runs
must
fall within the limits set by the venting
graph (see Figure 7).
Example 1:
For our shortest venting configuration use components A and E
(see
Figure 10)
.
Figure 10.
Typical Top Vent installation. If the 90° elbow is installed
directly on the fireplace, for height to the center of the
termination see chart on page 3.
Important:
An inspection of the explosion relief flappers and door must be
made prior to lighting the fireplace. This will ensure the door gas
-
keting material will provide an adequate seal during operation.
Horizontal Venting
Figure 11.
Typical Top Vent installation. The solid sections can be used in
various combinations to obtain the desired vent run. The vent
run
must
fall within the limits set by the venting graph.
90° Elbow
MEXT Section
PEXT Section
Termination
Example 2:
Rigid sections and an elbow used in conjunction with 3 ft. flex section
(MFL-3) will, when extended in a five foot chase, allow for a maximum
horizontal run of twelve and one-half feet from the centre of the fireplace
to outside wall and a minimum of 7'6" when retracted in opposite direction
(see Figure 12 and 13)
.
"C" flex sections and "D" rigid sections may be used in conjunction with
one another to obtain different possible horizontal length installations.
NOTE:
Flex section with no vertical rise must not exceed maximum
horizontal length of 3 feet
(see Figure 14)
. Flex runs over 3 feet must
fall within the limits set by the venting graph, and must have a minimum
vertical rise of 3" per foot of flex.
Installation