HWDF-Series Gas Fireplace
Part No. XG0190 - 071409
Installation
Figure 17.
Vertical venting with 2 offsets (1 offset= two
90° bends).
Figure 16.
Vertical venting with 1 offset (1 offset= two
90° bends).
Figure 19.
Extended installation.
Rear Vent Venting Runs
The
HW38-DF Rear Vent
has three possible installations which do not
require vertical lift, all of these installations require that you install the
RHS101 heat shield.
Heat Shield
The heat shield (RHS101) must be used on
all installations straight
through the wall
, at the point where the vent pipe connects to the
termination. With the heat shield, proper vent clearances can be
maintained.
The heat shield is not included with the fireplace.
To install the heat shield, slide one section over the vent pipe on the inside
of the wall opening, with the circular portion
inside the wall cavity
. Screw
the shield in place over the wall opening. Install the second section on
the outside of the wall opening sliding the circular portion into the wall
opening. Refer to Figure 19.
Figure 19.
Heat Shield. Install by sliding over the vent pipe where it
passes through combustible construction.
1. Straight Installation.
The height from the hearth to the center of the termination is 28
3/4". For straight installations use a 18" extension pipe (PXT-18)
with female/female connections. For shorter installations, cut the
PXT-18 to the desired length. Refer to figure 19.
Ensure that the RHS101 heat shield is installed before attaching
the pipe to the termination.
Note:
For Rear Vent models, maximum horizontal run with no
vertical lift must never exceed 18".
RHS101 Heat Shield
5/8, PXT18 ONLY
Flue Collar