C34-BV Gas Fireplace

Part  No.  XG0315

Installing The Gas Line

The gas line must be installed before finishing the C34-BV Fireplace.

Natural Gas

 requires a minimum  inlet gas supply  pressure of 5.5"

W.C. & a manifold pressure of 3.5" W.C. 

Propane Gas

 requires a

minimum inlet gas supply pressure of 11" W.C. & a manifold pressure
of 10" W.C. Provision must also be made for a 1/8" N.P.T. plugged
tapping and be accessible for test gauge connection immediately
upstream of the gas supply controls to the appliance. The fireplace gas
connection and the main operating gas valve is located behind the
removable brass trim at the bottom of the unit and need only be
attached to the gas line  with an approved fitting, as required by the

applicable installation codes

.

Installation

Note:

After gas line is connected, 

each 

appliance connection

,

valve  and  valve  train

  must  be  checked  while  under

normal operating pressure with either a liquid solution, or
leak detection device, to locate any source of leak. Tighten
any areas where bubbling appears or leak is detected until
bubbling stops completely or leak is no longer detected.

DO  NOT use a flame of any kind to test for leaks.

Installing The Remote Switch

The 

C34-BV'

s gas valve, located behind the lower brass trim, may be

connected to a wall switch. The valve generates its own power on

 a

millivolt circuit. Use only low voltage wire, and DO NOT

 connect

any external power to it.

Refer to Figure 12 for wiring requirements.

Note:

  The switch location must not exceed 30' from the fireplace.

Figure 5.  

Gas line access.

The appliance and its individual shutoff valve must be disconnected
from the gas supply piping system during any pressure testing of that
system at test pressures in excess of 1/2 psig (3.5 kPa).

The appliance must be isolated from the gas supply piping system by
closing its individual manual shutoff valve during any pressure testing of
the gas supply piping system at test pressures equal to or less than 1/2
psig (3.5 kPa).

B-Vent  Installation

The 

C34-BV 

is certified for use with standard 

4" B-Vent 

and requires

no B-Vent appliance connector. Simply attach the B-Vent to the
fireplace flue collar, and secure it using 1/4" sheet metal screws.

Refer to the current 

CAN/CGA B-149.1

 and

 .2

 or 

ANSI Z223.1-1988

Gas Installation Code

 for specific vent sizing.

n

Test your B-Vent installation after completion to ensure that no
combustible by-products are spilling from the fireplace opening.
This draft test should be performed after a three(3) minute warm
up period. The manufacturer will not be responsible for any
installations with inadequate draw.

CAUTION:

Note:

If more  than 12 feet of B-vent is used on the vent runs, use
ceiling supports

.

Summary of Contents for C34-BV

Page 1: ...Follow the gas supplier s instructions If you cannot reach your gas supplier call the fire department Warning Improper installation adjustment alteration service or maintenance can cause injury or property damage Refer to this manual For assistance or additional information consult a qualified installer service agency or the gas supplier For Your Safety Do not store or use gasoline or other flamma...

Page 2: ...esystem n Installation other than as instructed in this manual ConsultyourlocalGasInspectionBranchoninstallationrequirements for factory built gas fireplaces Installation repairs should be done by aqualifiedcontractor Installations in Canada must conform to the current CAN CGA B 149 1 and 2 Gas Installation Code and local regulations Installations in the USA must conform to local codes or in the a...

Page 3: ...tibles is 0 The C34 BV clearances to combustiblematerialsare Top 10 Back 0 Side 0 Floor 0 Mantle 8 B Vent up to 7 1 2 ft 2 Refer to page 5 Above 7 1 2 feet use clearances specified by the B ventmanufacturer Unprotected combustible walls which are perpendicular to the fireplace opening must not project beyond the shaded area shown in Figure 6b For protection against freezing temperatures it is reco...

Page 4: ...ind the lower brass trim may be connected to a wall switch The valve generates its own power on a millivolt circuit Use only low voltage wire and DO NOT connect any external power to it Refer to Figure 12 for wiring requirements Note The switch location must not exceed 30 from the fireplace Figure 5 Gas line access Theapplianceanditsindividualshutoffvalvemustbedisconnected from the gas supply pipi...

Page 5: ...6a Combustible mantles and facings Mantels Surrounds NOTE National Canadian Gas Association mantel test requirements are for fire hazard prevention to combustible materials New technology to meet consumer and government demands for the wise use of energy has prompted us to manufacture many models of fireplaces which are hot fuel and energy efficient Please be aware temperatures over the mantel wil...

Page 6: ...ure 9b Removing the door Removing and Installing the Door Removing the Door Remove the trim as described on the next page to access the door latches Open the latches by pulling Part A upwards and towards you to disengage Part B from the door Lift Part B clear of the door Repeat for all three latches Be sure to hold the door carefully so it does not fall See figure 9a Figure 9a Operating the door l...

Page 7: ... 3 upper and 3 lower whichmustbefield installed Install the trim by placing the top edge of the trim over to the retainer clips on either side of the fireplace Push the bottom edge firmly inwards and the trim will snap on See figure 11 Remember to slide the baffle into the top trim piece See Inset Note Baffle should rest on top of the tabs Inset Slide in baffle beforeinstallingtoptrim ...

Page 8: ... Model C34 BV 3 Push in gas control knob slightly and turn clockwise to Off Do not force 4 Flip up the lower trim 1 Turn off remote switch 2 Flip down the lower trim 1 STOP Read the safety information above on this label 2 Flip down the lower trims 3 Push in gas control knob and turn clockwise to OFF 4 Wait five 5 minutes to clear out any gas Smell for gas including near the floor If you then smel...

Page 9: ...ight any appliance n Do not touch any electrical switch do not use any phone in your building n Immediately call your gas supplier from a neighbour s phone Follow the gas supplier s instructions 1 Turn off remote switch 2 Flip down the lower trim 3 Turn the switch on the gas control to Off 4 Flip up the trim 1 STOP Read the safety information above on this label 2 Flip down the lower trims 3 Turn ...

Page 10: ...tions See pages 8 and 9 Burner Adjustment The C34 BV is equipped with an adjustable burner allowing you to raise or lower the flames To adjust the flames locate the black knob marked Hi Lo in the centre of the gas control valve See Figure 11 The front burners are not adjustable n To raise the flame height turn the black knob located behind the lower trim counterclockwise n To lower the flame heigh...

Page 11: ... SV9600 Check Transformer Line Volt Supply Replace SV9500 SV9600 Save old Igniter Flame Rod Assembly for service INSET HSI Terminals CHECK Line voltage power Low voltage transformer Limit Controller Thermostat Wiring Air proving switch on combustion air blower system Vent damper if used is open and end switch made C34 BV I Gas Control Valve Figure 12 Sit Nova 820 gas valve Pilot Burner Adjustment ...

Page 12: ...sandwillresultinafirehazard Limitations On Liability Limitations On Liability Limitations On Liability Limitations On Liability Limitations On Liability ItisexpresslyagreedandunderstoodthatTheCompaniessoleobligation andpurchaser sexclusiveremedyunderthisWarranty underanyotherwarranty expressed orimplied orincontract tortorotherwise shallbelimitedtoreplacement repair orrefund asspecifiedabove Innoe...

Page 13: ...Page 13 C34 BV Gas Fireplace Part No XG0315 Notes ...

Page 14: ...Canadian Heating Products Inc Langley BC V4W 4A1 Montigo Del Ray Corp Ferndale WA 98248 XG0315 Rev 0 April 10 01 ...

Reviews: