Page 5
BF-Series-ST Gas Fireplace
Part No. XG0711 - 022410
f i r e f e a t u r e
Installation
“W”
108”
“Y”
“X”
“Z”
“X1”
“X”
W
Y
X1
BF52-30
94
64
27
BF52-36
X
Z
60
BF60-48
102
94
42
48
64
72
27
27
67
73
85
BF84
94*
96*
94*
28*
*
Figure 2.
Framing dimensions and clearances to combustibles.
Figure 3.
Framing dimensions side view.
WARNING!
When this appliance is installed directly on carpeting, tile or any
combustible material other than wood flooring, it must be installed
on a metal or wood panel extending the full width and depth of
the appliance.
Control Cable
Connection to
Electrical Box
Gas Line
access.
Installing The Gas Line
The gas line must be installed before finishing the
BF-ST
Fireplace.
Natural Gas
requires a minimum inlet gas supply pressure of 5.5"
W.C. & a manifold pressure of 3.5" W.C.
Propane Gas
requires a
minimum inlet gas supply pressure of 11" W.C. & a manifold pressure
of 10" W.C. Provision must also be made for a 1/8" N.P.T. plugged
tapping and be accessible for test gauge connection immediately
upstream of the gas supply controls to the appliance. The fireplace
gas connection and the main operating gas valve is located behind
the removable brick panel in the centre of the unit. It only needs to be
attached to the gas line with an approved fitting, as required by the
applicable installation codes
.
The appliance and its individual shutoff valve must be disconnected
from the gas supply piping system during any pressure testing of that
system at test pressures in excess of 1/2 psig (3.5 kPa).
The appliance must be isolated from the gas supply piping system by
closing its individual manual shutoff valve during any pressure testing
of the gas supply piping system at test pressures equal to or less than
1/2 psig (3.5 kPa).
Figure 4.
Gas line access.
All dimensions, and design specifications are
subject to approval upon quotation of fire-
place and associated equipment.
Important:
*Check with manufacturer prior to framing