9
Setup
1) Set the Output Source switch (S2) to 12 or 24VDC as dictated by the voltage rating
of the lock being used.
2) Set the Output Mode switch to LIMIT when used with Brute electric lock or a similar
heavy-duty solenoid operated lock. Set this switch to DIRECT when used with
standard electric strikes or magnetic locks.
3) Set the # of Digits switch (S4) to the desired number of PIN digits (3, 4 or 5).
4) Set the valid PIN code using the Digit DIP switches. DIP switches for unused digits
should all be set to OFF.
5) Set the Duration control (R19) to the approximate desired open time (minimum of 3
seconds, maximum of 60 seconds) by adjusting the potentiometer.
6) Set the Penalty control (R8) to the approximate desired penalty time (minimum of 3
seconds, maximum of 60 seconds) by adjusting the potentiometer.
7) Connect the power cord to an appropriate source of AC power and verify that the
Power LED illuminates.
8) Enter the valid PIN code on the keypad and verify that the lock releases and that the
green LED on the keypad illuminates.