Monessen • Glow Getter Owner’s /Installation Manual • 4606-900 Rev. A • 8/17
Do not install the heater:
•
Where curtains, furniture, clothing, or
other flammable objects are less than
36" from the front of the heater.
•
In high traffic areas.
•
In windy or drafty areas.
WARNING
WARNING
Gloves are recommended when handling
logs to prevent skin irritation from loose
fibers. Logs are fragile—handle with care.
Placement in Fireplace with a Restrictive Barrier
The following are guidelines for placing a gas log set in a
fireplace that has a restrictive barrier of the fireplace for
vented appliance only.
Height of Restriction
(x)
Minimum Depth of
Fireplace/Firebox
No Restriction
14"
0" to 1
1
⁄
2
"
16"
Greater than 1
1
⁄
2
" to 3"
16"
Greater than 3"
*
*Any barrier greater than 3" placed in front of the gas log set is not
recommended by the manufacturer.
NOTE:
Non-combustible material such as refractory brick
may be used to line the floor of the fireplace in order to raise
the height of the gas log set in relation to a restrictive barrier.
If the unit is raised, the minimum height dimension listed
in the homeowner’s manual must be met or exceeded.
NOTE:
If the log set is equipped with a remote receiver, a
restrictive barrier may reduce the battery life by increasing
the ambient temperature inside the fireplace. Placement
of the receiver outside of the fireplace will extend the
battery life.
Barriers such as the bottom of a glass door frame
placed in front of a gas log set can change the air
flow characteristics of the fireplace which in turn
can cause the unit to overheat and malfunction when
installed as a vented log set.
WARNING
Glass door frames with adjustable louvers
should have the louvers fully open while
the unit is in operation
Depth of fire
-
place/firebox
(Refer to table)
The log set should be placed against
or as near as possible to the rear
wall of the fireplace/firebox.
Height of restrictive barrier caused by glass
door frames, recessed fireplaces, etc. from
the base or bottom surface of the unit.
(Refer to table)
Figure 2.2 - Reference Drawing of a Natural Flame Log Set in
an Enclosure with Glass Door or Barrier Installed
DO NOT INSTALL ANY GLASS OR BARRIERS ON A
VENTLESS FIREBOX
WARNING
F. Millivolt Ignition Controls
Natural Gas:
An external regulator is required to reduce
supply pressure to a maximum of 10-1/2” w.c. on natural
gas systems operating at higher pressure.
The piezo ignitor allows ignition of the pilot without the use
of matches or batteries.
Milivoit control has four (4) positions:
OFF:
All gas to the gas logs is shut off at the valve.
IGN:
Valve position to light/maintain a standing pilot.
ON:
Valve position to turn ON/OFF log set with remote
switch/thermostat.
LOW/HI:
Variable position to control flame height (heat
output).
The gas log heater is fitted with a specially designed safety
pilot (ODS assembly) which senses the amount of oxygen
available in the room and shuts the gas log heater off if the
oxygen level begins to drop below a satisfactory level. The
pilot can only be relit when adequate fresh air is available.
G. Pilot/ODS