background image

SPECIAL REQUIREMENTS CONTINUED

2.   APPROVED CARBON MONOXIDE DETECTORS. Each carbon monoxide detector as required in accor-

dance with the above provisions shall comply with NFPA 720 and be ANSI/UL 2034 listed and IAS certi-
fi ed. 

3.   SIGNAGE. A metal or plastic identifi cation plate shall be permanently mounted to the exterior of the build-

ing at a minimum height of eight (8) feet above grade directly in line with the exhaust vent terminal for the 
horizontally vented gas fueled heating appliance or equipment. The sign shall read, in print size no less 
than one-half (1/2) inch in size, 

“GAS VENT DIRECTLY BELOW. KEEP CLEAR OF ALL OBSTRUC-

TIONS.”

4.   INSPECTION. The state or local gas inspector of the side wall horizontally vented gas fueled equipment 

shall not approve the installation unless, upon inspection, the inspector observes carbon monoxide detec-
tors and signage installed in accordance with the provisions of 248 CMR 5.08(2)(a)1 through 4. 

(b)  EXEMPTIONS: The following equipment is exempt from 248 CMR 5.08(2)(a)1 through 4: 

1.   The equipment listed in Chapter 10 entitled “Equipment Not Required To Be Vented” in the most current 

edition of NFPA 54 as adopted by the Board; and 

2.   Product Approved side wall horizontally vented gas fueled equipment installed in a room or structure 

separate from the dwelling, building or structure used in whole or in part for residential purposes. 

(c)  MANUFACTURER REQUIREMENTS - GAS EQUIPMENT VENTING SYSTEM PROVIDED. When the manu-

facturer of Product Approved side wall horizontally vented gas equipment provides a venting system design or 
venting system components with the equipment, the instructions provided by the manufacturer for installation 
of the equipment and the venting system shall include:

1.   Detailed instructions for the installation of the venting system design or the venting system components; 

and

2.   A complete parts list for the venting system design or venting system. 

(d)  MANUFACTURER REQUIREMENTS - GAS EQUIPMENT VENTING SYSTEM NOT PROVIDED. When the 

manufacturer of a Product Approved side wall horizontally vented gas fueled equipment does not provide the 
parts for venting the fl ue gases, but identifi es “special venting systems,” the following requirements shall be 
satisfi ed by the manufacturer:

1.   The referenced “special venting system” instructions shall be included with the appliance or equipment 

installation instructions; and 

2.   The “special venting systems” shall be Product Approved by the Board, and the instructions for that system 

shall include a parts list and detailed installation instructions. 

(e)  A copy of all installation instructions for all Product Approved side wall horizontally vented gas fueled equip-

ment, all venting instructions, all parts lists for venting instructions, and/or all venting design instructions shall 
remain with the appliance or equipment at the completion of the installation. 

Summary of Contents for 724BV4536NE

Page 1: ...TO HIGH TEMPERATURES THE APPLIANCE SHOULD BE LOCATED OUT OF TRAFFIC AND AWAY FROM FURNITURE AND DRAPERIES CHILDREN AND ADULTS SHOULD BE ALERTED TO THE HAZARDS OF HIGH SURFACE TEMPERATURE AND SHOULD S...

Page 2: ...NG VENT COMPONENTS 11 BEFORE YOU START 11 PIPING INSTALLATIONS 11 VENT TERMINATION 13 OUTSIDE AIR KIT INSTALLATION 14 GAS LINE AND ELECTRICAL 15 GAS LINE INSTALLATION 15 ELECTRICAL WIRING 16 FINAL INS...

Page 3: ...xternal vent cap on a regular basis to make sure that no debris is interfering with the airflow Provide adequate clearances around air openings and adequate accessibility clearance for servicing and o...

Page 4: ...ltitudes up to 2000 ft When installing this fireplace at an elevation above 2000 ft it may be necessary to decrease the input rating by changing the existing burner orifice to a smaller size Input sho...

Page 5: ...ation of your appliance This includes determining where the unit is to be installed the vent configuration to be used framing and finishing details and whether any optional accessories i e wall switch...

Page 6: ...P PR RE E I IN NS ST TA AL LL LA AT TI IO ON N I IN NF FO OR RM MA AT TI IO ON N Figure 1 Fireplace Dimensions 5...

Page 7: ...T TI IO ON N I IN NF FO OR RM MA AT TI IO ON N Figure 2 Fireplace Locations and Minimum Clearances Requirements CAUTION Measure fireplace dimensions and verify framing methods wall covering details be...

Page 8: ...bottom of the appliance Refer to Figure 3 Back wall Clearance The appliance may be placed against a combustible back wall NOTE There are 1 4 ribs spacers on the outer shell of the unit to maintain mi...

Page 9: ...hard combustible surface i e flat wood plywood or particleboard Be sure that the fireplace rests on a solid continuous floor or platform with appropriate framing support Do NOT install appliance direc...

Page 10: ...le materials i e brick tile slate steel or other materials with a UL fire rating of Zero may be used to cover the black surface of the appliance A 300 F minimum adhesive may be used to attach facing m...

Page 11: ...tion and frame later Be sure fireplace is resting on a flat surface 3 Set unit level and plumb by checking the top and front of unit Shim side to side and front to back as necessary 4 Anchor nailing f...

Page 12: ...the manual with the termination cap thoroughly before installing unit or vent system After vent configuration has been decided begin attaching pipe to unit Piping Installations 1 Attached the first pi...

Page 13: ...om the pipe manufacturer To Locate and Install Ceiling Firestop For ceiling firestops position a plumb bob over the center of the vertical pipe to spot a hole through which the pipe will penetrate Dri...

Page 14: ...r building codes specify a minimum vent height above the rooftop depending on the pitch of the roof Refer to the above figure for minimum heights provided the termination cap is at least eight 8 feet...

Page 15: ...en it meets the roof Attach a storm collar over the flashing joint to form a watertight seal Place non hardening mastic around the joint between the storm collar and the vertical pipe Attach terminati...

Page 16: ...le valve key for safety In this case remove factory shut off valve from the flex line and connect line direct to stub WARNING Support the shut off valve when attaching 1 2 gas line Use a wrench to hol...

Page 17: ...ectrical Code ANSI NFPA 70 latest edition or the Canadian Electrical Code CSA C22 1 Label all wires prior to disconnection when servicing controls Wiring errors can cause improper and dangerous operat...

Page 18: ...ol Refer to Figure 13 Wiring Diagram for Standing Pilot Millivolt System The millivolt system and individual components may be checked with a millivolt meter having 1 1000 mV range Conduct each check...

Page 19: ...main burner does not come on then replace control valve 9 If meter is reading less than 175 millivolt then refer to TROUBLESHOOTING section of this manual to determine the cause of the low reading El...

Page 20: ...due to high temperatures inside the chamber This will prevent failures and longer battery life 1 Plug in the remote connector wire to the remote receiver 2 Connect the wire terminal from the remote re...

Page 21: ...top edge of the fireplace but must never overlap the black metal face The black metal face may be covered with non combustible material only After applying the finishing material a non combustible sea...

Page 22: ...in bottom of log with grate bar Step 3 Place Front Right Log 3 on right front of grate bar lining up cutout in bottom of log with grate bar Make sure Log 3 touches Log 1 Step 4 Place back end Top Mid...

Page 23: ...ned or completely closed 1 Remove and discard the two 2 screws that secure the C Channel below the top opening of the fireplace 2 Attach bottom rail 1 to unit with 2 sheet metal screws 3 Refer to Figu...

Page 24: ...igure 22 WARNING Damper must be in open position when appliance main burner is operating The damper system must be LOCKED into the OPEN position during operation If damper is not open the appliance wi...

Page 25: ...every second Subsequent lighting of the fireplace will not require this purging of air from the gas lines unless the gas valve has been shut off for a long period Lighting the Fireplace You may notice...

Page 26: ...next step 6 Find Pilot located under the log 7 Turn gas valve counterclockwise to Pilot 1 Open left side access door 2 Turn RS OFF ON rocker switch to OFF 3 Push in gas valve knob slightly and turn c...

Page 27: ...burner by hand Electronic Gas Valve LIGHTING INSTRUCTIONS ELECTRONIC IGN 1 Turn RS OFF ON rocker switch to OFF 2 Turn off all electric power to the appliance if service is to be performed TO TURN OFF...

Page 28: ...the pilot should be visually checked as soon as the heater is installed and periodically during normal operation The pilot flame must always be present when the fireplace is in operation Refer to Fig...

Page 29: ...roken Caution Replace any glass that is chipped cracked or broken Replacement glass door assemblies MUST be supplied by the fireplace manufacturer Warning No substitute materials may be used Warning H...

Page 30: ...Firebrick right side 1 26D7135 26D7135 2d Firebrick center 42 1 26D7138 3 Pull Screen 1 MS MS 4 Bi Fold Brass Black Doors 1 BBD4536 BLD4536 BBD5142 BLD5142 5 Manual Remote Control 1 RCM RCB RCM RCB 6...

Page 31: ...lve 1 23D6046 23D6046 23D6046 23D6046 5 Rocker Switch 1 41D0048 41D0048 41D0048 41D0048 6 Piezo Igniter 1 14D0503 14D0503 14D0503 14D0503 7 Injector 1 32D0100 32D0118 32D0100 32D0118 8 Burner Assembly...

Page 32: ...cker Switch 1 41D0048 41D0048 41D0048 41D0048 7 Injector 1 32D0100 32D0118 32D0100 32D0118 8 Burner Assembly 1 41D0500K 41D0501K 41D0500K 41D0501K 9 Wire Assembly 1 54D2007 54D2007 54D2007 54D2007 14...

Page 33: ...nection Place jumper wires across terminals of switch If burner comes on replace defective switch If the switch is OK repeat the same procedure on remote control If burner comes on replace remote cont...

Page 34: ...ELECTRONIC IGNITION 33...

Page 35: ...ed by a decorative enclosure Remove or open enclosure or raise cap above it B Cap is crushed damaged or missing Replace cap 4 Poor draft due to ext environment A Buildings trees roof lines interfering...

Page 36: ...ve finished grade in the area of the venting including but not limited to decks and porches the following requirements shall be satisfied 1 INSTALLATION OF CARBON MONOXIDE DETECTORS At the time of ins...

Page 37: ...d in whole or in part for residential purposes c MANUFACTURER REQUIREMENTS GAS EQUIPMENT VENTING SYSTEM PROVIDED When the manu facturer of Product Approved side wall horizontally vented gas equipment...

Page 38: ...if the appliance is not operated and maintained according to the operating instructions supplied with the appliance and does not extend to 1 firebox burner assembly damage by accident neglect misuse...

Reviews: