Actuators

Technical Data

Technical Information

OEM-Actuator

Type

A 4004 / A  4104

Version

normally closed / normally open

Voltage

24 V AC/DC, +20%...–10%, 0–60 Hz

Max. inrush current

250 mA during 2 min max.

Operating current

75 mA

Operating power

1.8  W

Closing and opening times

approx. 3 min.

Actuator travel

4 mm

Actuating force

100 N ± 5%

Fluid temperature

0 - 100 °C

 1)

Storage temperature

-25 to +60°C

Ambient temperature

0 to +60°C

Protection type / protection class

IP 54 

2) 

/ III

CE conformity according to

EN 60730

Housing / housing colour

Polyamide / grey

Weight 

100 g with a 1 m connecting cable

Connecting cable / length 

3)

2 x 0.75 mm

2

 PVC, grey / 1 m

Technical changes reserved. 8-D58-40-342 Index 25. Reprint, in whole or in part, is only admissible with our approval.

Characteristic Curves

Normally Closed (NC)

Normally Open (NO)

max

4
3
2
1
0

max

4
3
2
1
0

on

off

voltage on

time

make

break

stroke [mm]

voltage

time

dead

time

hold time

on

off

voltage on

time

make

break

stroke [mm]

voltage

time

dead

time

hold time

Möhlenhoff Wärmetechnik GmbH
Museumstraße 54a
38229 Salzgitter / Germany

T49 (0)53 41·8475-0
Telefax  +49 (0)53 41·8475-99

E-Mail: [email protected]
Internet: www.moehlenhoff.com

OEM-Actuator with valve adapter

1) in dependence of the adapter even higher
2) in all installation positions
3) special length on demand, but < 5.0 m
4) referring to standard valves

Planning and Installation Notes

Valve Adaptation

Installation Positions

Valve adaptation is archived by a valve adapter which is available in

different versions to suit the most common valve bottoms and heating

circuit distributors (please consider when ordering).

Prefered installation positions of the OEM-Acutator are vertical and

horizontal. An up-side down position may reduce product life through

special circumstances (e.g. contaminated water).

Calculation of maximum cable length (copper cable) for 24 V rated voltage

L = K 

x

 A / n

A

Conductor cross-section in mm²

n

Number of Actuators

K

Constant (269 m/mm

2

)

L  Cable length in m

We recommend the following cables for installing a 24 V system:
Bell wire:

Y(R)

0,8 mm

2

Light plastic-sheathed cable: NYM

1,5 mm

2

Flat webbed building wire: NYIF

1,5 mm

2

Transformer:
A safey isolating transformer according to EN 61558-2-6 (Europe) or class
II FCC-quality proofed (North America) must always be used. Transformer
dimensioning results from the making capacity of the OEM-Actuators.
Rule-of-thumb formula:

P

Transformer

 = 6 W x

n = number of OEM-Actuators

Connections Overview

24 V AC

  L1

L2

OEM-Actuator

A 4004 / A 4104

time-switch

Thermostat

R 20..

+4 mm

47 mm

54 mm

 

4)

44 mm

Reviews: