42
DEU
ENG
NDL
FRA
ITA
ESP
No. Parameters
Description
Unit
142 Follow-up time
Time elapsing from the moment of switching off the
switching outputs until the boiler relay is actually
switched off.
[min]
Standard: 0
143 Control direction switch-
ing outputs
The relay function can be inverted if used as a
control output.
normal=0
inverted=1
Standard: 0
144
Boiler control
Normal: No disconnection of the boiler relay in the PWM
pauses
Direct: Disconnection of the boiler relay in the PWM
pauses
The same function mode of the boiler relay must be
selected in all bases of the master-slave system.
The line-up/follow-up times remain.
normal=0
direct=1
Standard: 0
160 Antifreeze protection
Activation of control outputs for T
actual
<x °C
(x = parameter 161)
Deactivated=0
Activated=1
Standard: 1
161 Antifreeze temperature
Antifreeze function limit value
[°C]
Standard: 8
170 Smart Start
Learning-in of the temperature behaviour of the
individual heating zones
Deactivated=0
Activated=1
Standard: 0
Operating lock (hotel function)
171
Hotel function
Switch-over of the room control unit operating lock between
“Standard” and “Restricted operation” (hotel function).
Standard=0
Restricted opera-
tiong=1
Standard: 0
Emergency operation
180 Duration until activation
Duration until the activation of the emergency
operation routine
[min]
Standard: 180
181 PWM cycle duration in
emergency operation
Duration of a PWM cycle in emergency operation
[min]
Standard:15
182 Cycle duration PWM
heating
Control duration in heating operation
[%]
Standard: 25
183 Cycle duration PWM
cooling
Control duration in cooling operation
[%]
Standard: 0
Valve protection function
190 Duration until activation
Starting time after last activation
[d]
Standard: 14
191 Valve activation duration
Valve activation duration (0= function deactivated)
[min]
Standard: 5
Pump protection function
200 Duration until activation
Starting time after last activation
[d]
Standard: 3
201 Activation duration
Activation duration (0 = function deactivated)
[min]
Standard: 5
210 First open function (FO)
Activation of all switching outputs at power-up
[min]
Off=0
Standard: 10