Software Configuration
46
06/99 AWB 2700-1364 GB
:
Configuration 1:
for PS 4-271-MM1
Configuration 2:
for PS 4-201-MM1
PS 4-271-MM1
PS 4-201-MM1
PS 4-201-MM1
Configuration
Station
Parameters
Configuration 1
PS 4-271-MM1
Suconet K master,
e.g. 375 kBaud
PS 4-201-MM1
Receive data
1)
: e.g. 40
Send data
2)
: e.g. 38
CRC
5)
: e.g.
✓
(yes)
Configuration 2
PS 4-201-MM1
Suconet K slave
Receive data
3)
: e.g. 38
Send data
4)
: e.g. 40
Remote Control: e.g.
✓
(yes)
1) Receive data,
for master
Number of bytes the master is to receive from the
slave. Must agree with the number of send data
bytes in the configuration for the slave.
2) Send data,
for master
Number of bytes the master is to send to the slave.
Must agree with the number of receive data bytes in
the configuration for the slave.
3) Receive data
for slave
Number of bytes the slave is to receive from the
master. Must agree with the number of send data
bytes in the configuration for the master.
4) Send data
for slave
Number of bytes the slave is to send to the master.
Must agree with the number of receive data bytes in
the configuration for the master.