Suconet K interface
17
06/99 AWB 2700-1364 GB
If it is not possible to achieve equal ground
potentials, connect the PC to the mains supply via an
isolating transformer or use a laptop powered by an
internal battery.
Suconet K interface
Connector pin assignment
Figure 7: Pin assignment of Suconet K interface (right-hand
socket, top view)
Connecting to the Suconet K field bus
왘
Use the KPG 1-PS3 bus cable to connect
additional Suconet K stations (PS 4, EM 4) to the
PS 4-271 compact PLC.
5-pin DIN connector (pin)
5-pin DIN connector (pin)
1--------------------------------1
4--------------------------------4
Warning!
To prevent potential equalisation currents arising
between the PLC and PC, devices attached to
the PRG and Suconet K interfaces must have the
same ground potential. If the ground potentials
differ, the interfaces can be destroyed.
PIN 1
Data cable RS 485, Suconet K (TB/RB)
PIN 2, 3, 5 Assigned internally
PIN 4
Data cable RS 485, Suconet K (TA/RA)
3
5
2
4
1
The interface is also used for connecting the
ZB 4-501-TC1 telecontrol module and the ZB 4-
501-UM3 interface converter.