![Moeller CM4-505-GV1 Hardware And Engineering Download Page 26](http://html1.mh-extra.com/html/moeller/cm4-505-gv1/cm4-505-gv1_hardware-and-engineering_1819328026.webp)
AS-i/PROFIBUS Gateway
PROFIBUS-DP
is
s
u
e
d
a
te
2
2
.6
.2
0
0
1
26
Delta List: List of AS-i slaves with configuration error:
1: ConfigError
0: no ConfigError
LPF:List of AS-i slaves with peripery fault:
1: periphery fault
0: no periphery fault
LCS: List of Corrupted slaves (see chapter 6).
Each element of the user diagnosis (ec-flags and slave lists) can be switched off by
setting the appropriate bit in the parameter telegram.
Each element that is not used will be filled up with zeros. This way the data elements
in the diagnosis telegram will keep its designated position (and clear text diagnosis
fits to the data furthermore).
Only if an element at the end of the user diagnosis is not used, the length of the diag-
nosis will be shortened.
Extdiag will be set if at least one of the following conditions is fulfilled:
• ConfigError
≡
1
• APF
≡
1
• PeripheryFault
≡
1
• LCS is not empty
The conditions when to set the ExtDiag bit can be chosen using the user parameters
or the mailbox commands.
The GSD file includes the following presettings:
• The PROFIBUS diagnosis displayes: EC-flags, delta list and LPF. The LCS is not
displayed.
• ExtDiag will be set if ConfigError =1 and APF = 1. ExtDiag will not be set if the is a
periphery fault or if there is a entry in the LCS.
If an AS-i/PROFIBUS-DP Gateway with 2 AS-i masters is used, the User-Diagnosis-
Bytes 5 to 30 represent AS-i network 1 and the User-diagnosis bytes 31 to 56 repre-
sent AS-i network 2.
User Parameters
With the User Paramters can be selected which slave liste will be displayed in the
PROFIBUS diagnosis. Furthermore can be selceted which conditions have to be ful-
filled to set the ExtDiag bit within the diagnosis telegram..
DP Parameters
PDU byte
user byte
DP
DPV1
user
default
1
–
station_status
✔
2
–
WD_Fact_1
✔
3
–
WD_Fact_2
✔
4
–
min T
sdr
✔
5
–
ident high
✔
6
–
ident low
✔
Summary of Contents for CM4-505-GV1
Page 2: ......
Page 6: ...AS i PROFIBUS Gateway The Used Symbols issue date 22 6 2001 6 ...
Page 8: ...AS i PROFIBUS Gateway Safety issue date 22 6 2001 8 ...
Page 16: ...AS i PROFIBUS Gateway Connections Displays and Operating Keys issue date 22 6 2001 16 ...
Page 22: ...AS i PROFIBUS Gateway Operating the AS i PROFIBUS Gateway issue date 22 6 2001 22 ...
Page 62: ...AS i PROFIBUS Gateway PROFIBUS DP issue date 22 6 2001 62 ...
Page 68: ...AS i PROFIBUS Gateway Commissioning Tools and Accessories issue date 22 6 2001 68 ...
Page 77: ......