![Moeller CM4-505-GV1 Hardware And Engineering Download Page 24](http://html1.mh-extra.com/html/moeller/cm4-505-gv1/cm4-505-gv1_hardware-and-engineering_1819328024.webp)
AS-i/PROFIBUS Gateway
Advanced Diagnostics for AS-i Masters
is
s
u
e
d
a
te
2
2
.6
.2
0
0
1
24
6.3
Off-line Phase on Configuration Errors (LOS)
The AS-i masters with advanced diagnostics offer the possibility to put themselves
into the off-line Phase when a configuration error on the AS-Interface occurs. In this
way the security of the application can be ensured. The reaction to a configuration er-
ror is very fast and the host can be relieved from this task. If there are any problems
on the AS-i network, the AS-interface can be switched to a secure state.
There are two different ways to parameterize the AS-i master for this feature:
• Every configuration error during normal operation in protected mode releases the
off-line phase.
• For each slave address can be chosen whether a configuration error on this ad-
dress will release the off-line phase or not. This information is stored in the List of
Off-line Slaves (
LOS
).
The user himself can decide how the system reacts to a configuration error on the
AS-Interface. The AS-i master can release the off-line phase in critical situations,
i.e. only with certain slave addresses, while in less critical situations (if one of the
other AS-i slaves have a configuration error) only the error message configuration
error is sent to the host, but AS-i is still running.
The parameterization of off-line phase on configuration error is also supported by the
"AS-i Control Tools".
Summary of Contents for CM4-505-GV1
Page 2: ......
Page 6: ...AS i PROFIBUS Gateway The Used Symbols issue date 22 6 2001 6 ...
Page 8: ...AS i PROFIBUS Gateway Safety issue date 22 6 2001 8 ...
Page 16: ...AS i PROFIBUS Gateway Connections Displays and Operating Keys issue date 22 6 2001 16 ...
Page 22: ...AS i PROFIBUS Gateway Operating the AS i PROFIBUS Gateway issue date 22 6 2001 22 ...
Page 62: ...AS i PROFIBUS Gateway PROFIBUS DP issue date 22 6 2001 62 ...
Page 68: ...AS i PROFIBUS Gateway Commissioning Tools and Accessories issue date 22 6 2001 68 ...
Page 77: ......