Connection to PROFIBUS-DP
68
11/01 AWB2700-1426GB
Parameterization for
XStart
Each XStart module requires 3 bytes of parameters in the
PROFIBUS-DP telegram. The following table shows the struc-
ture of these 3 bytes.
Table 11: Parameters for XStart
Byte
Bit
Parameter name
Value
Meaning
0
0
trip indicating AGM
0
without AGM
1)
1
with AGM
4
kind of power module
0
direct-on-line-starter
1)
1
reversing starter
1
4 to 0
power level
00010
0.06 kW
1)
00011
0.09 kW
00100
0.18 kW
00101
0.25 kW
00110
0.55 kW
00111
0.75 kW
01000
1.5 kW
01001
2.2 kW
2
3 to 0
no. accepted higher kW rating
s
2)
0000
0
1)
0001
1
0010
2
0011
3
0100
4
0101
5
0110
6
0111
7
7 to 4
AGM: accepted deviation
2)
0000
identification
necessary
1)
0001
deviation accepted