![Moeller 15-V-SWD Hardware And Engineering Download Page 38](http://html1.mh-extra.com/html/moeller/15-v-swd/15-v-swd_hardware-and-engineering_1819339038.webp)
Switching on Contactors DIL-
SWD-32-001, DIL-SWD-32-002
34
Table 3:
Power consumptions of the contactor coils with a
voltage of 24 V DC
Contactor
Pick-up power
Pick-up
current with
24 V DC
Sealing power
Holding
current with
24 V DC
[W]
[mA]
[W]
[mA]
DIL7 - DIL9
3
125
3
125
DIL12 - DIL15
4.5
188
4.5
188
DIL17 - DIL38
12
500
0.5
21
h
Caution!
The sum of the pick-up power of the simultaneously
tripping contactors and the sum of the holding power of
the tripped contactors for each SmartWire-Darwin
network must not exceed 72 W. If required, an additional
power feeder module (EU5C-SWD-PF1-1, EU5C-SWD-PF-
2) must be used (
chapter "Power Module EU5C-SWD-
h
The DIL modules draw their energy for the communication
electronics and for activation of the LEDs and of the
auxiliary switches from the SmartWire-Darwin network
supply. Please take into consideration the total current
consumption of your SmartWire-Darwin network and, if
necessary, plan for an additional feeder module EU5C-
SWD-PF2-1.
h
For data for the current requirement please refer to the
table in the appendix on page 103.
Summary of Contents for 15-V-SWD
Page 8: ...4 02 09 AWB2723 1613en ...
Page 34: ...30 02 09 AWB2723 1613en ...
Page 64: ...60 ...
Page 106: ...102 02 09 AWB2723 1613en ...
Page 128: ...124 02 09 AWB2723 1613en ...