![Moeller 15-V-SWD Hardware And Engineering Download Page 17](http://html1.mh-extra.com/html/moeller/15-v-swd/15-v-swd_hardware-and-engineering_1819339017.webp)
EU5C-SWD-PF2-1
13
02/09 AWB2723-1613en
Installation
The SmartWire-Darwin power module EUSC-SWD PF2 is
envisaged for mounting on a top hat rail.
X
Mount the module on the top hat rail.
X
Connect the 24 V DC voltage to the terminals POW on the
front of the module.
X
If necessary, reconnect the 24 V DC voltage for the
contactor coils to the terminals AUX.
X
Connect the 8-pole SmartWire-Darwin cable to the SWD In
socket. The continuation to the next SmartWire-Darwin
module is from the SWD Out socket.
The connection terminals are suitable for cables AWG24 to
AWG16. and flexible cables with a cross section of 0.5 mm2
to 1.5 mm
2
.
Figure 4:
Terminal capacity
• fine wire, cross-section 0.25 mm² to 1.5 mm², with the
ferrule (minimum length 8 mm.)
• Solid: 0.14 mm² to 1.5 mm²
3
A
3
A
3
A
24 V DC
0 V