![Moeller 15-V-SWD Hardware And Engineering Download Page 116](http://html1.mh-extra.com/html/moeller/15-v-swd/15-v-swd_hardware-and-engineering_1819339116.webp)
Appendix
112
02/09 AWB2723-1613en
Digital inputs
Number
8
4
4
Input current
m A
typ. 4 at 24 V DC
Voltage level to IEC/EN 61131-2
Limit value type 1
Low < 5 V DC; High > 15 V DC
Input delay
High
r
Low typ. < 0.2 ms
Low
r
High typ. < 0.2 ms
Status display inputs
LED
yellow
Digital semiconductor outputs
Number
–
4
–
Output current
A
–
typ. 0.5 at 24 V
DC
–
Short-circuit detection threshold A
–
max. 1.2 over 3
ms
–
Lamp load
R
LL
W
–
3
–
Overload proof
–
yes, with
diagnostics
–
Switching capacity
–
EN 60947-5-1
utilization
category DC-13
–
Relay outputs
Number
–
–
2
Contact type
–
–
N/O contact
Operations
Utilization category AC-1, 250 V, 6 A
–
–
> 6 x 10
4
Utilization category AC-15, 250 V, 3 A –
–
> 5 x 10
4
Utilization category DC-13, 24 V, 1 A
–
–
> 2 x 10
5
Safe isolation
V AC
–
–
230
minimum load current
m A
–
–
100 mA , 12 V DC
Response/reset time
ms
–
–
5/2.5
Bounce duration
ms
–
–
Normally 1.5
Short-circuit protective device
–
–
external 4 A gL/
gG
Status display outputs
LED
–
yellow
yellow
EU5E-SWD-
8DX
EU5E-SWD-
4D4D
EU5E-SWD-
4D2R