2-506.14
Figure 4.3 - Unit Suspension Method of Vertical
Delivery Units
Model VE Unit Suspension
There are four tapped holes (1/2''-13) in the top of the unit for
unit suspension. Unit suspension can be made with threaded
rods, pipes, or ceiling hanger brackets furnished by others.
See Figure 4.3.
Model PTE Unit Suspension
Model PTE electric heaters are provided with four hanger
brackets for installation with four ceiling suspension rods (5/8-
inch diameter), furnished by others. Refer to Figures 4.4 and 5.1.
NOTE: A pipe hanger adapter kit is available as an accessory
from Modine. The kit consists of two drilled 3/4'' I.P.S. pipe caps
and two 1/2''-13 x 1 3/4'' capscrews to facilitate threaded-pipe
suspension. Two kits are required to pipe-mount a vertical unit.
Kit is not available on 480-volt models, VE50 thru VE250 with
transformer junction box.
INSTALLATION
Figure 4.4 - Ceiling-mounted Model PTE
Figure 4.1 - Vertical Model VE with Cone Jet
Accessory Installed
ANGLE
BRACKET
FASTENING
Figure 4.2 - Horizontal Delivery with Louver Deflectors
(Models PTE300, PTE400, PTE500)
MODEL
HEIGHT (H)
THROW (T)
PTE300
17 75
PTE400
15 60
PTE500
14 45
H
T
Be sure the means of suspension is adequate to support
the weight of the unit. For proper operation, the unit must
be installed in a level horizontal position. Clearances to
combustibles as specified above must be strictly maintained.
Do not install unit heater above the maximum mounting height
shown in Table 3.1 for VE models or Figure 3.4 for PTE models
or below eight feet.
4