Dual Fuel Setup / Thermostat Wiring
When matched with an A-coil and a furnace for the air handler,
a dual fuel thermostat is required to prevent furnace from
engaging when heat pump is operating. The heat pump is the
first and second stage of heating and the furnace is the auxiliary
heat.
Condensate Overflow Alarm
Modine Air Handlers and Cased / Uncased A-coils are supplied
with a condensate pan overflow switch which should be wired
back to the Split System with two wires. Terminals are provided
in control panel for field wiring of condensate overflow switch.
Remove the blue jumper wire and wire COS to terminals 533 &
534. Refer to wiring diagram and Figure 12.2.
If the Modine Split unit is matched with an existing air handler or
air coil, it is highly recommended a normally closed, condensate
overflow switch is installed in the air coil drain pan and wired to
the unit control board. When installed, the controller will shut
down the unit in the event of a plugged condensate drain line.
Failure to wire the switch to unit may result in damage to the
furnace or property.
The condensate switch accessory assembly, 3H0387860001, is
available for field installation. It is supplied with 75’ of lead wire.
The condensate alarm is a 24V, normally closed, dry contact.
The installer may route the leads back to the unit or run two
wires.
Open Loop Control Valve Wiring
Always maintain water pressure in the heat exchanger by placing
water control valves at the outlet of the unit to prevent mineral
precipitation during the off cycle. Pilot operated slow closing valves
are recommended to reduce water hammer. If water hammer
persists, an expansion tank can be mounted on the piping to help
absorb the excess hammer shock. Slow closing valve must have
an end switch that enables/disables the compressor. See valve
manufacturer's instructions for proper wiring.
500
〈
〈
C
24VAC Common
502
〈
〈
R
24VAC Hot
520
〈
〈
G
Fan
521
〈
〈
Y1
Compressor Stage 1
522
〈
〈
Y2
Compressor Stage 2
591
〈
〈
W1
Aux Ht Stg 1
592
〈
〈
W2
Aux Ht Stg 2