Gas Pressure Table - KS1460 Single/Double
Gas Type
Natural Gas
ULPG/
Propane
Minimum Inlet Pressure - Pre-Regulator
1.13 kPa
2.75 kPa
Maximum Inlet Pressure - Pre-Regulator
5.0 kPa
5.0 kPa
Operating pressure - Post-Regulator (Point A)
1.0 kPa
2.3 kPa
Operating Pressure when on high - (Point B)
0.75 kPa
1.66 kPa
Operating Pressure when on low - (Point B)
0.42 kPa
0.8 kPa
Remove the small access hatch found on top of the engine.
Loosen test point A (shown in the first diagram of this section) and attach a manometer tube in
preparation for measuring the operating pressure—post regulator.
Turn the fire on high and adjust the operating pressure at the regulator (shaded grey in the diagram
below)
Once the operating pressure—post regulator—is set, check the operating pressure at test point A or B
(shown in the first diagram of this section).
Changing the Operating Pressure from the Remote
The following instructions
must only be undertaken by a suitably approved
person
. Any tampering by an unauthorised person will void the product’s
warranty and may result in a dangerous condition.
While the remote is in its “OFF” mode with only the time showing on the
display, press the MINUS, PLUS and FAN BOOST buttons simultaneously
(as shown right) until the characters “03” light up on the display. Release the
buttons and the remote will count down and display “GO”. The screen will
then display all characters and should be reading 00. This will put the remote
into test mode.