LP-446-r4 Rev. 10.12.16
7
Part 2 - Before You Start
CAUTION
VWH units must be connected to a storage tank. You must not have a direct connection of the potable water system into the heat
exchanger. This could cause flow issues, short cycling, and an increase of mineral build-up in the unit. This system is designed
to have incoming potable water flow through the storage tank first, then through the heat exchanger. Failure to connect the
VWH boiler to a storage tank of the minimum size requirements (119 gallons for a single 500VWH; 175 gallons for a single
700/850VWH) will result in property damage and/or premature boiler failure. Damages resulting from incorrect installation or
from use of products not approved by HTP, Inc. ARE NOT covered by warranty.
∆T
(Delta T)
(
o
F)
500VWH
700VWH
850VWH
Gallons
Per Hour
First
Hour
Rating
119
Gallon
Tank
First
Hour
Rating
175
Gallon
Tank
First
Hour
Rating
200
Gallon
Tank
Gallons
Per Hour
First
Hour
Rating
119
Gallon
Tank
First
Hour
Rating
175
Gallon
Tank
First
Hour
Rating
200
Gallon
Tank
Gallons
Per Hour
First
Hour
Rating
175
Gallon
Tank
First
Hour
Rating
200
Gallon
Tank
First
Hour
Rating
300
Gallon
Tank
Contact HTP for Available
Storage Tanks
Contact HTP for Available
Storage Tanks
Contact HTP for Available
Storage Tanks
40
o
1414
859
883
894
1980
1206
1217
1260
2404
1449
1459
1502
50
o
1131
872
902
915
1584
1225
1238
1292
1923
1467
1481
1534
60
o
943
884
920
937
1320
1244
1260
1324
1602
1486
1502
1566
70
o
808
897
939
958
1131
1262
1281
1356
1374
1505
1524
1599
80
o
707
910
958
979
990
1281
1303
1388
1202
1524
1545
1631
90
o
628
923
977
1001
880
1300
1324
1420
1068
1542
1566
1663
100
o
566
935
995
1022
792
1319
1345
1453
961
1561
1588
1695
110
o
514
948
1014
1044
720
1337
1367
1485
874
1580
1609
1727
120
o
471
961
1033
1065
660
1356
1388
1517
801
1599
1631
1759
130
o
435
974
1052
1087
609
1375
1410
1549
740
1617
1652
1791
140
o
404
986
1070
1108
566
1394
1431
1581
687
1636
1674
1824
Table 2 - VWH Ratings with Storage Tanks - NOTE: Gallons Per Hour Does Not Take a Storage Tank into Account
Min Tank Size (Gal.) = Required Flow (GPM) X 10
Mixing Factor (M
f
) = VWH Outlet Temp - Inlet Temp
70
First Hour Rating = Total VWH Output X VWH Efficiency + .75 X Total Storage X M
f
[
(VWH Outlet Temp - Inlet Temp) X 8.31
]
Example:
2 500VWH Boilers - Total Output = 1,000,000 BTU @ 94% Efficiency
VWH Outlet Temp = 140
o
F - Inlet Temp = 40
o
F
2 Storage Tanks (119 Gallons Each) =Total Storage = 238 Gallons
Mixing Factor (M
f
) = 140 - 40
= 1.43
70
First Hour Rating = 1,000,000 X .94 + .75 X 238 X 1.43
[
(140 - 40) X 8.31
]
First Hour Rating = 940,000 + 179 X 1.43
[
831
]
First Hour Rating = [1,131 + 179] X 1.43
First Hour Rating = 1,310 X 1.43
First Hour Rating = 1,873 Gallons
Summary of Contents for MODCON500
Page 35: ...LP 446 r4 Rev 10 12 16 35 Figure 29 Cascade Master and FollowerWiring...
Page 57: ...LP 446 r4 Rev 10 12 16 57 Figure 35 500 Model Combustion System Replacement Parts...
Page 58: ...LP 446 r4 Rev 10 12 16 58 Figure 36 700 850 Models Combustion System Replacement Parts...
Page 60: ...LP 446 r4 Rev 10 12 16 60 Figure 38 Cabinet Replacement Parts All Models...