LP-446-r4 Rev. 10.12.16
6
NEVER use any toxic chemical, including automotive, standard
glycol antifreeze, or ethylene glycol made for hydronic (non-
potable) systems. These chemicals can attack gaskets and seals
in water systems, are poisonous if consumed, and can cause
personal injury or death.
UNCRATING THE BOILER
- Any claims for damage or
shortage in shipment must be filed immediately against the
transportation company by the consignee.
Households with small children, disabled, or elderly persons
may require a 120
o
F or lower temperature setting to prevent
severe personal injury or death due to scalding.
G. Water Temperature Adjustment
If the boiler is going to have a set temperature above 120
o
F, you
must use an ASSE 1017 rated mixing valve to avoid severe burns
or death from scalding temperatures.
Approximate Time / Temperature Relationships in Scalds
120
o
F
More than 5 minutes
125
o
F
1 1/2 to 2 minutes
130
o
F
About 30 seconds
135
o
F
About 10 seconds
140
o
F
Less than 5 seconds
145
o
F
Less than 3 seconds
150
o
F
About 1 1/2 seconds
155
o
F
About 1 second
Table 1 - Approximate Time / Temperature Relationships in Scalds
Failure of the boiler due to freeze related damage IS NOT
covered by product warranty.
E. Freeze Protection
NOTE:
Consider piping and installation when determining boiler
location.
D. Boiler Water
Do not use petroleum-based cleaning or sealing compounds in
a water heating system. Gaskets and seals in the system may be
damaged. This can result in substantial property damage.
Do not use “homemade cures” or “patent medicines”. Damage
to the boiler, substantial property damage, and/or serious
personal injury may result.
F. High Elevation Installations
Natural gas at high elevation might contain less heating value
than typical 1,000 BTU/cu ft and therefore can cause improper
air / gas mix leading to improper combustion. For natural gas
installations above 3,000 ft, call your gas provider to determine
the heating value of the supplied natural gas.
Summary of Contents for MODCON500
Page 35: ...LP 446 r4 Rev 10 12 16 35 Figure 29 Cascade Master and FollowerWiring...
Page 57: ...LP 446 r4 Rev 10 12 16 57 Figure 35 500 Model Combustion System Replacement Parts...
Page 58: ...LP 446 r4 Rev 10 12 16 58 Figure 36 700 850 Models Combustion System Replacement Parts...
Page 60: ...LP 446 r4 Rev 10 12 16 60 Figure 38 Cabinet Replacement Parts All Models...