161
Reference Manual
IP2048/RM, Rev AA
Appendix F: Configuring Using HART
January 2015
F.4.15
Pulses in use (D918)
This is the actual number of pulses transmitted in the previous burst of pulses.
Note
The factory default setting is to automatically decide the number of pulses in a burst for
optimum performance (see
Target Pulses
on
page 139
)
Field Communicator
To view the number of pulses being used in a burst:
1.
From the
Home
screen, select
3: Service Tools
.
2.
Select
1: Alerts
.
3.
Select
2: Diagnostic Data
.
4.
Select
3: Operation
.
5.
Select
3: Pulses In Use D918
.
6.
When finished, press
EXIT
to exit to the previous menu.
Note
This is also at the Fast Key sequence 2, 2, 7 [or 8], 5, 2
(see
Appendix E: Field Communicator
).
Mobrey MCU900 Series control unit
To view the number of pulses being used in a burst:
1.
From the
Main Menu
screen, select
MONITOR
.
2.
Select the transmitter (e.g. “
Tx1:MSP400RH
”).
3.
Select
DIAGNOSTICS
.
4.
Select
OPERATION
.
5.
Select
Pulses In Use
.
6.
When finished, press the
ESC
key to exit to the previous menu.
Fast Keys
3, 1, 2, 3, 3
Pulses in Use D918
10
EXIT
HELP
(Field Communicator Screen)
Pulses in Use D918
10
(Mobrey MCU901 Screen)
Summary of Contents for MSP400RH
Page 2: ......
Page 4: ......
Page 16: ...6 Reference Manual IP2048 RM Rev AA Section 2 Transmitter Overview January 2015 ...
Page 54: ...44 Reference Manual IP2048 RM Rev AA Section 4 Starting up January 2015 ...
Page 80: ...70 Reference Manual IP2048 RM Rev AA Appendix A Reference Data January 2015 ...
Page 84: ...74 Reference Manual IP2048 RM Rev AA Appendix B Product Certifications January 2015 ...
Page 87: ...77 Reference Manual IP2048 RM Rev AA Appendix C Integrated Display Menus January 2015 ...
Page 90: ...80 Reference Manual IP2048 RM Rev AA Appendix C Integrated Display Menus January 2015 ...
Page 98: ...88 Reference Manual IP2048 RM Rev AA Appendix E Field Communicator January 2015 ...