Appendix F: Configuring Using HART
January 2015
F.3.18
Upper range value (P015)
This defines the process value (PV) represented by a 20 mA output from the transmitter.
The span of the 4–20 mA current output is defined by the
Upper Range Value
parameter and
the
Lower Range Value
parameter (
page 126
).
Consider a tank with a 120 gallons capacity. When full, a 20 mA output current is required from
the transmitter. Therefore, the upper range value is set to 120 if the PV is in gallon units. The
lower range value is typically set to 0 (gallons) for the 4 mA output to indicate an empty tank.
The upper range value can be less than the lower range value, in which case the current output
will decrease for an increasing process value (PV).
Note
The upper range value is
automatically overwritten
when the
Tank Shape/NLP
parameter is
used to select a flume flow profile, but the populated value can still be edited if required.
See
Table F-1 on page 119
for the 20 mA point values.
The displayed units are selected using the parameter
Primary Variable Units
(see
page 120
). Changing units does not re-scale the upper range value.
Field Communicator
To view or change the upper range value:
1.
From the
Home
screen, select
2: Configure
.
2.
Select
2: Manual Setup
, and then
1: Basic Setup
.
3.
Select
3: Upper Range Value P015
.
4.
If a change is required:
(
a
) Input a new value, and then select “
ENTER
” to save it.
(
b
) Press “
SEND
” to update the transmitter.
Note
When messages appear, take appropriate action if needed and press “
OK
”.
Mobrey MCU900 Series control unit
To view or change the upper range value:
1.
From the
Main Menu
screen, select
SETUP
.
2.
Select the transmitter (e.g. “
Tx1: MSP400RH
”).
3.
Select
OUTPUT
,
CURRENT
, and then
Up Range Val
.
4.
Follow the on-screen instructions to edit and save the new setting.
(Press the
Enter
(
) key if prompted to change mode to “
off-line
”).
5.
Select “
Quit
” to exit to the previous menu.
Fast Keys
2, 2, 1, 3
Upper Range Value P015
34.5 ft
34.5
ESC
DEL
ENTER
HELP
w
s
q
a
z
Lock
Shift
@ &
á ü
x
e
d
c
r
f
v
t
g
b
y
h
n
u
j
m
*
-
+
/
.
0
7
4
1
8
5
2
9
6
3
i
k
o
l
FN
(Field Communicator Screen)
Up Range Val P015
34.500ft
Esc=Quit =Edit
(Mobrey MCU901 Screen)
Summary of Contents for MSP400RH
Page 2: ......
Page 4: ......
Page 16: ...6 Reference Manual IP2048 RM Rev AA Section 2 Transmitter Overview January 2015 ...
Page 54: ...44 Reference Manual IP2048 RM Rev AA Section 4 Starting up January 2015 ...
Page 80: ...70 Reference Manual IP2048 RM Rev AA Appendix A Reference Data January 2015 ...
Page 84: ...74 Reference Manual IP2048 RM Rev AA Appendix B Product Certifications January 2015 ...
Page 87: ...77 Reference Manual IP2048 RM Rev AA Appendix C Integrated Display Menus January 2015 ...
Page 90: ...80 Reference Manual IP2048 RM Rev AA Appendix C Integrated Display Menus January 2015 ...
Page 98: ...88 Reference Manual IP2048 RM Rev AA Appendix E Field Communicator January 2015 ...