© MOBATIME
82 / 94
801299.00
B
Alarm list
Nr.
Error message
Description
Action
Chap.
0
Reboot DTS
DTS 4020 restarted
no intervention required
1
System warning
Internal System Warning
Check dts.log for detail Warning
information
2
Supply voltage too low
Power failure (internally
measured)
support
3
Failure red. supply
Power failure redundant supply
(only if redundant supply is on)
Check in the menu which
power supply fails
4
Internal voltage to low
Power failure (internally
measured)
support
5
Error bit 5
Not used
6
To high offset to PTP
To high offset to PTP
check PTP time source
7
Error bit 7
Not used
8
Too high offset to FREQ
To high offset to Frequency-In
check FREQ time source
9
Too high offset to E1
To high offset to E1
check E1 time source
10
PTP synch lost
check PTP time source
11
Error bit 11
Not used
12
FREQ synch lost
check FREQ time source
13
Error bit 13
Not used
14
Error bit 14
Not used
15
Time source big offset
Big offset to time source detected
check time source
16
Time source fail stratum
Stratum too high
check time source
17
Failure time source TO
No time information from the
selected time source within the
configured timeout
check time source
In slave mode: check link
18
No valid time
20 min after starting no valid time
Check time source
19
NTP synch lost
Check NTP configuration
20
Too high offset to NTP
Check NTP time source
21
NTP Error
NTP not running
Check NTP configuration
22
Error bit 22
Not used
23
No valid time source
Check synchronization and
source settings
24
No mail server
No connection to configured mail
server
Check e-mail configuration,
check connection
25
SNMP Error
SNMP not running
Check SNMP and trap
configuration
26
Error bit26
Not used
27
Error bit27
Not used
28
Error bit28
Not used
29
NTP Configuration Error
Configured NTP Authentication
Key is not correct
Check the configured NTP
trusted keys against imported
key file.
Check the configured keys
for multicast against configured
trusted keys
see dts.log file for details
6.5.12
30
Error bit 30
Not used
31
Error bit 31
Not used
32
Error bit 32
Not used
33
Error bit 33
Not used
34
Oscillator not locked
During start-up / first time synch:
During normal operation:
normal behavior, no action
support
Oscillator not
locked