• Remove the gear tray from the baseplate by pinching the clips at two locations (see Fig. 2)
INSTALLATION & MAINTENANCE MANUAL
These instructions should be read carefully and retained after installation by the end user for future reference
and maintenance.
These instructions should be used to aid installation of the following products:
AC65136EM / AC65158EM / AC651581EM / AC65170EM / AC65236EM / AC65258EM / AC652581EM /
AC65270EM
SAFETY
•
This product must be installed in accordance with the latest edition of the IEE Wiring Regulations
(BS7671) and current Building Regulations. If in any doubt, consult a qualified electrician
•
Please isolate mains prior to installation or maintenance
•
Check the total load on the circuit (including when this luminaire is fitted) does not exceed the rating of
the circuit cable, fuse or circuit breaker
•
Please note the IP (Ingress Protection) rating of this luminaire/product when deciding the location for
installation
•
This product is Class I and must be earthed
•
This product is IP65 rated
INSTALLATION
•
Provide power to the required point of installation
•
Unfasten the clips on either side of the fitting (see Fig. 1) and remove the diffuser
Fig. 1
•
Remove the gear tray from the baseplate by pinching the clips at two locations (see Fig. 2)
Fig. 2
•
Mark the location of the fixing holes and drill the holes ensuring not to infringe with any gas/water pipes
or electrical cables. Fixing centres are shown in Fig. 3
Fig. 2
• Mark the location of the fixing holes and drill the holes ensuring not to infringe with any gas/water pipes or
electrical cables. Fixing centres are shown in Fig. 3
Fig. 3
•
Drill out one of the 20mm drilling guides and fit the compression gland provided
•
Feed the mains cable into the luminaire, and tighten the compression gland ensuring a tight seal is
made
•
Ensuring correct polarity is observed, carefully wire as shown in Fig. 4
Fig. 4
•
Ensure the battery is connected via the plug and socket to the emergency inverter
•
Replace the gear tray
•
Fit an appropriate T8 fluorescent tube
•
Replace the diffuser
•
Switch on and check for correct operation, ensuring the green indicator LED is illuminated
•
We recommend, on commissioning the installation, a minimum charge period of 24 hours before
carrying out an emergency duration test
•
If the batteries have been left in a discharged state for an extended period, we recommend that one or
more charge and discharge cycles are completed which should help to restore the battery capacity
WARNING
This product must be disconnected from the circuit if subjected to any high voltage or insulation resistance
testing. Irreparable damage will occur if this instruction is not followed.
GENERAL
This product contains a control gear which can be replaced by a professional.
Fig. 3
• Drill out one of the 20mm drilling guides and fit the compression gland provided
• Feed the mains cable into the luminaire, and tighten the compression gland ensuring a tight seal is made
• Ensuring correct polarity is observed, carefully wire as shown in Fig. 4