-
21
-
(2)
Within 30 minutes after either auto or manual operation stops, if auto operation is started, or if you switch to auto operation during
manual operation, the system runs in the previous operation mode.
(3)
The temperature is checked 1 time in 30 minutes after the start of operation, and if the judgment differs from the previous operation
mode, the operation mode changes.
(4)
Setting temperature can be adjusted within the following range. There is the relationship as shown below between the signals of the
wireless remote control and the setting temperature.
Signals of wireless remote control (Display)
–6
–5
–4
–3
–2
–1
±
0
+1
+2
+3
+4
+5
+6
Setting
Cooling
18
19
20
21
22
23
24
25
26
27
28
29
30
temperature
Dehumidifying
18
19
20
21
22
23
24
25
26
27
28
29
30
Heating
20
21
22
23
24
25
26
27
28
29
30
31
32
4.12 Regulation of outdoor air flow
The fan operates as follows according to the outdoor air temperature. (Except during defrost.)
S
SRK52 HE, 63 HE
Cooling, thermaldry
Heating
Outdoor air temp. (˚C)
32
2nd speed
1st speed
30
Outdoor air temp. (˚C)
12
2nd speed
1st speed
10
S
SRK71 HE
Cooling, thermaldry
Heating
Outdoor air temp. (˚C)
25
2nd speed
1st speed
23
3rd speed
32
30
Outdoor air temp. (˚C)
12
2nd speed
1st speed
10
3rd speed
18
16