Note (1) The number of flashes when in the Service Mode do not include the 1.5 second period when the lights light up at first (starting signal). (See the example

shown below.)

0.5 sec.

1.5 sec.

RUN light

(10’s digit)

TIMER light

(1’s digit)

11-second interval

0.5 sec.

OFF

ON

OFF

ON

 In the case of current cut (example: stop code “42”)

The RUN light (10’s digit) flashes 4 times and the TIMER light (1’s digit) flashes 2 times.

×

 10 + 2 

×

 1 = 42 

 From the table, read the instructions for error code 42, “Current cut”.

Notes

 (2) Error display:

- Is not displayed. (automatic recovery only)

 Displayed.

If there is a (     ) displayed, the error display shows the number of times that an auto recovery occurred for the same reason has reached
the number of times in (     ).
If no (     ) is displayed, the error display shows that the trouble has occurred once.

Notes

 (3) Auto Recovery:

- Does not occur

 Auto recovery occurs.

(d)

Remote control information tables

1) Operation switching

RUN light

(Operation switching)

Display pattern when

in service mode

Operation switching

when there is an

abnormal stop

0

1

2

3

4

AUTO

DRY

COOL

FAN

HEAT

2) Fan speed switching

TIMER light

(Fan speed switching)

Display pattern when

in service mode

Fan speed 

switching when 

there is an 

abnormal stop

0

2

3

4

6

7

AUTO

HI

MED

LO

HI POWER

ECONO

* If no data are recorded (error code is normal), the information display in the remote control becomes as follows.

Remote control setting

Operation switching

Fan speed switching

Display when error code is normal.

AUTO

AUTO

0.5 sec.

1.5 sec.

RUN light

(10’s digit)

TIMER light

(1’s digit)

11-second interval

0.5 sec.

OFF

ON

OFF

ON

(Example): Operation switching, fan speed switching, cooling  HI

Summary of Contents for SRK50ZHX-S

Page 1: ...3 INVERTER WALL MOUNTED TYPE ROOM AIR CONDITIONER Split system air to air heat pump type SRK50ZHX S SRK60ZHX S Manual No 08 SRK T 079...

Page 2: ...n 9 4 3 Auto restart function 9 4 4 Custom cord switching procedure 9 4 5 Flap and louver control 10 4 6 3D auto operation 11 4 7 Timer operation 12 4 8 Installation location setting 12 4 9 Outline of...

Page 3: ...or electrical equipment 30 6 2 Servicing 48 7 REFRIGERANT PIPING INSTALLATION SERVICING MANUAL FOR AIR CONDITIONERS USING R410A 49 7 1 Outline 49 7 2 Refrigerant piping installation 50 7 3 Installatio...

Page 4: ...ess remote control Flap swing The flaps swing up and down successively Louver swing The louvers swing left and right successively 3D auto operation Fan speed and air flow direction are automatically c...

Page 5: ...OWER Green 3D AUTO Green ECONO Blue Safety equipment O D mm in Liquid line 6 35 1 4 Gas line 12 7 1 2 Connecting method Flare connecting Attached length of piping Liquid line 0 55 m Gas line 0 49 m In...

Page 6: ...een TIMER Yellow HI POWER Green 3D AUTO Green ECONO Blue Safety equipment O D mm in Liquid line 6 35 1 4 Gas line 12 7 1 2 Connecting method Flare connecting Attached length of piping Liquid line 0 55...

Page 7: ...imately 15 to 30 C Cooling operation Approximately 15 to 46 C Heating operation Approximately 15 to 21 C Power source voltage Rating 10 Voltage at starting Min 85 of rating Frequency of ON OFF cycle M...

Page 8: ...12 2 R6 2 4 Piping system Models SRK50ZHX S 60ZHX S Outdoor unit Indoor unit Room temp sensor Heat exchanger Flare connection Heat exchanger sensor 1 Piping Liquid 6 35 Check joint 4 way valve Service...

Page 9: ...How to obtain the cooling and heating capacity Example The net cooling capacity of the model SRK60ZHX S with the piping length of 15m indoor wet bulb temperature at 19 0 C and outdoor dry bulb tempera...

Page 10: ...G RD RD BK BK WH WH YE BL T 1 Phase 220 240V 50Hz 1 3 4 5 5 5 2 12 5 5 5 5 5 5 5 5 5 6 Th1 SM3 SM4 SM2 SM1 SM5 LS Th2 Th3 FM Powewr Source INTERFACE KIT SC BIKN DISPL BACK U WIRELESS RECEIVER HEAT EXC...

Page 11: ...LEAN mode ON TIMER button This button selects ON TIMER operation AIR FLOW LEFT RIGHT button 3D AUTO button This button sets 3D AUTO operation This button selects ALLERGEN CLEAR operation ALLERGEN CLEA...

Page 12: ...ngs b HIGH POWER operations Notes 1 Auto restart function is set at on when the air conditioner is shipped from the factory Consult with your dealer if this function needs to be switched off 2 When po...

Page 13: ...memorized in the microcomputer the flap or louver will automatically be set at this angle when the next operation is started 5 When not operating The flap returns to the position of air flow directly...

Page 14: ...termined according to the room temperature and setting temperature 2 During DRY Operation including auto DRY operation At cooling Air flow selection Operation mode AUTO HI MED LO At heating Room temp...

Page 15: ...the side walls If you set the remote control s installation position keep it so that the air flow is within the range shown in the following figure 1 Setting 1 If the air conditioning unit is running...

Page 16: ...when all of the following conditions are met 1 After start of heating operation When it elapsed 35 minutes Accumulated compressor operation time 2 After end of defrosting operation When it elapsed 35...

Page 17: ...e outdoor air temperature determines the operation mode and then begins in the automatic operation Heating Dehumidifying Cooling Room temperature C Outdoor temperature C 2 The unit checks the temperat...

Page 18: ...an that after fuzzy calculation the speed is kept to 30 rps However when the thermo becomes OFF the speed is reduced to 0 rps c Reset conditions When either of the following condition is satisfied 1 T...

Page 19: ...Prevents anomalous high pressure operation during heating b Detector Indoor heat exchanger sensor Th2 c Detail of operation A B C D Indoor unit heat exchanger temperature C 4rps 1 8rps 2 8rps 2 4rps...

Page 20: ...control is activated and inching prevention control is carried out with the minimum speed set at 35 rps 4 The outdoor fan is set on 2nd speed 5 The indoor fan is stepped up by 1 speed step Upper limi...

Page 21: ...9 Current safe a Purpose Current is controlled not to exceed the upper limit of the setting operation current b Detail of operation Input current to the converter is monitored with the current sensor...

Page 22: ...plement the following controls 1 Outdoor heat exchanger temperature 21 C After the outdoor fan speed drops down to 1 speed for 60 seconds if the outdoor heat exchanger temperature is lower than 21 C g...

Page 23: ...the proper cable and insure that the external force of the cable is not conducted to the terminal connection part through properly securing it Improper connection or securing can result in heat genera...

Page 24: ...taken in performing a welding operation near this unit and take necessary precautions to prevent spatters from entering this unit For installation work be careful not to get injured with the heat exch...

Page 25: ...irect sunlight or near heat devices such as a stove 3 Outdoor unit a Where air is not trapped b Where the installation fittings can be firmly installed c Where wind does not hinder the intake and outl...

Page 26: ...al between them as a service space In order to facilitate servicing of controllers please provide a sufficient space between units so that their top plates can be removed easily 4 Where a danger of sh...

Page 27: ...ge Sealing plate Sleeve Indoor side Outdoor side Standard hole 450 Level position 2 locations Fixing on concrete wall Use of nut anchor Use of bolt anchor Nut M6 Mounting board Mounting board Max 10 B...

Page 28: ...H05RNR4G1 5 Example or 245IEC57 H Harmonized cable type 05 300 500 volts R Natural and or synth rubber wire insulation N Polychloroprene rubber conductors insulation R Standed core 4or5 Number of cond...

Page 29: ...nit from the installation board 1 Push up at the marked portion of the indoor unit base lower latch and slightly pull it toward you both right and left hand sides The indoor unit base lower latch can...

Page 30: ...ified torquing value Liquid side 6 35 14 18N m 1 4 1 8kgf m Gas side 12 7 49 61N m 4 9 6 1kgf m Use one more spanner to fix the valve Remove the flared nuts on both liquid and gas sides Remove the fla...

Page 31: ...Please use an anti reverse flow type vacuum pump adapter so as to prevent vacuum pump oil from running back into the system Oil running back into an air conditioning system may cause the refrigerant c...

Page 32: ...Cooling 35 C DB 24 C WB Heating 7 C DB 6 C WB Low pressure MPa Temp difference between return air and supply air C High pressure MPa 220 230 240V b When manipulating the remote control mounted on a w...

Page 33: ...nt service valve open 3 Troubleshooting procedure If the air conditioner does not run at all If the air conditioner does not run at all diagnose the trouble using the following troubleshooting procedu...

Page 34: ...ble and perform an operation check The air conditioning system is operating normally Replace the faulty component then perform an operation check Identify the faulty component by using the check proce...

Page 35: ...lower than the set value The air conditioner stops When the power transistor is judged breakdown while compressor starts The compressor is stopped Broken compressor wire Compressor blockage Trouble o...

Page 36: ...y a stop occurred when the air conditioning system performed protective stops etc in the past Even if stop data alone are generated the system restarts automatically After executing the stop mode whil...

Page 37: ...error code was displayed in the past Displays the indoor heat exchanger sensor temperature at the time the error code was displayed in the past Displays the remote control information at the time the...

Page 38: ...r code 2 times previous when an error was displayed Displays the reason for the stop error code 3 times previous when an error was displayed Displays the reason for the stop error code 4 times previou...

Page 39: ...causing faulty operation When 7 minute 35 seconds passes without communications signals from either the outdoor unit or 2 time flash 39 Discharge pipe sensor is abnormal anomalous stop When a tempera...

Page 40: ...s in If no is displayed the error display shows that the trouble has occurred once Notes 3 Auto Recovery Does not occur Auto recovery occurs d Remote control information tables 1 Operation switching R...

Page 41: ...46 56 66 76 86 96 57 47 37 27 17 7 7 17 27 37 47 57 67 77 87 97 58 48 38 28 18 8 8 18 28 38 48 58 68 78 88 98 59 49 39 29 19 9 9 19 29 39 49 59 69 79 89 99 No does not sound If no data are recorded e...

Page 42: ...94 114 134 56 36 16 16 36 56 76 96 116 136 58 38 18 18 38 58 78 98 118 138 No does not sound If no data are recorded error code is normal the display for each sensor becomes as shown below Sensor name...

Page 43: ...trol information on fourth previous occasion Outdoor air temperature sensor temperature on fourth previous occasion Outdoor heat exchanger sensor temperature on fourth previous occasion Discharge pipe...

Page 44: ...0 1 9 55 14 125 1 6 60 12 130 1 4 65 10 135 1 3 Discharge pipe sensor temperature characteristics Indoor fan motor error Defective fan motor connector poor connection defective PCB Is connector connec...

Page 45: ...ent gas refrigerant Does compressor operation Is output voltage applied to all 3 phases of power transistor Replace compressor Replace heat exchanger sensor Insufficient gas Is refrigerant amount norm...

Page 46: ...ission Wiring error including power cable defective indoor outdoor unit PCB Does error persist after power reset Are the lines connecting the indoor and outdoor units connected normally Is DC 0 Approx...

Page 47: ...ty reading is 0 Anti condensation control is not done 12 Disconnected wire 1 and 2 are short Humidity reading is 100 Anti condensation control keep doing circuited Disconnected wire Short Circuit Rema...

Page 48: ...ndoor unit fan motor check procedure This is a diagnostic procedure for determining if the indoor unit s fan motor or the circuit board is broken down 1 Indoor unit printed circuit board output check...

Page 49: ...serial signal inspection to AC 220 230 240V 1 to 2 AC 220 230 240V 2 to 3 Normal if the voltage oscillates between DC 0 and approx 20V CAUTION HIGH VOLTAGE High voltage is produced in the control box...

Page 50: ...rol NO YES Normal Power transistor inspection procedure Use a tester with a needle indicator for the inspection Do not use a digital tester Check in the AC 300 volt range 1 If there is a self diagnosi...

Page 51: ...en immediately retighten it after observing that gas is blow out from the loosened portion e Open the valve 1 and 3 after discharging air from the charge hose A then the liquid refrigerant begins flow...

Page 52: ...s Pseudo azeotropic characteristics R410A is a pseudo azeotropic mixed refrigerant composed of two constituents R32 and R125 Quasi azeotropic condition refers to a state in which the dew point curve a...

Page 53: ...isonous gas may occur 5 When an air conditioning system charged with a large volume of refrigerant e g multi type air conditioner is installed in a small room it is necessary to exercise care so that...

Page 54: ...ce outer diameter Minimum joint thickness diameter of copper pipe jointed mm mm 1 4 6 35 0 50 3 8 9 52 0 60 1 2 12 70 0 70 5 8 15 88 0 80 7 2 2 Processing of piping materials When performing the refri...

Page 55: ...1 4 6 35 0 8 0 0 5 1 0 1 5 1 5 2 0 3 8 9 52 0 8 0 0 5 1 0 1 5 1 5 2 0 1 2 12 70 0 8 0 0 5 1 0 1 5 2 0 2 5 5 8 15 88 1 0 0 0 5 1 0 1 5 2 0 2 5 Table 6 Dimensions related to flare processing for R22 No...

Page 56: ...and which contains less contaminants It is necessary to carefully treat store copper pipes so that they are not collapsed deformed or damaged Due care must also be exercised so that foreign matters su...

Page 57: ...ing the connected parts As brazing is molten between the joined surfaces to yield high adhesive strength it is necessary to secure a wide enough space to be joined and also an adequate clearance betwe...

Page 58: ...ssium fluoride potas sium chloride and sodium fluoride to the borax boric acid compound Cautions 1 Remove the flux after brazing 2 When chlorine contained in the flux stays within the pipe the lubrica...

Page 59: ...cloth and 3 by means of heat absorbent 4 Movement during brazing Eliminate all vibration during brazing to protect brazed joints from cracking and breakage 5 Oxidation preventive In order to improve...

Page 60: ...o types of electronic balance for refrigerant charging are available one for 10kg cylinder and the other for 20kg cylinder Electronic balance for 10kg cylinder precision 2g Electronic balance for 20kg...

Page 61: ...cking for refrigerant cylinder According to the charge hose s cap size a charge port with 1 2 UNF 20 threads per inch and corresponding packing are required j Gas leakage detector A high sensitivity g...

Page 62: ...e to make setting so that liquid can be charged When using a cylinder equipped with a siphon liquid can be charged without turning it upside down b Connect the gauge manifold s charge hose to the elec...

Page 63: ...e indoor outdoor units Caution When storing the indoor unit piping in its original position be careful not to break the piping 2 Installing the unit a Proceed with the installation following the steps...

Page 64: ...reventing function float switch moisture indicator drier and other accessory functions should be adjusted or replaced where necessary 4 Electrical circuit b Checking the accessories to the refrigerant...

Page 65: ...cessories tools are required Shown below are standard accessories 1 Recovering cylinder Use a recovering cylinder designated by the equipment manufacturer A detachable cylinder must be such that it co...

Page 66: ...iercing valve a A tool used to make a hole for recovery in the copper pipe when recovering R410A from equipment which has no port for charging or recovering gas Various types are available on the mark...

Page 67: ...2 INVERTER WALL MOUNTED TYPE ROOM AIR CONDITIONER No 116 1 1A R Air Conditioning Refrigeration Systems Headquarters 16 5 2 chome Kounan Minato ku Tokyo 108 8215 Japan Fax 03 6716 5926...

Reviews: