112
(6)
Indoor electrical components inspection flow-chart
Note (1) Excepted 50 model
Is there voltage between terminal
blocks
1
and
2
? (AC 220/230/240 V)
Indoor electrical components
are normal.
Is there voltage between CNC (1)
and (2)
on the secondary side of the
transformer? (Approx. 12 V)
Is the voltage between terminal
blocks
2
and
3
oscillating between
DC 0 and 12V?
Inspect power source
for outdoor unit.
Replace fuse.
Replace the transformer.
Replace printed
circuit board.
Is the fuse burnt out? (3.15 A)
YES
YES
YES
YES
NO
NO
NO
NO
(5)
How to make sure of remote controller
Is remote
controller
normal?
YES
Again pushing
operating switch
Operating the unit?
NO
Does backup
switch operates?
Operating the unit.
NO
NO
YES
YES
Remote controller
defects
Abnormality is not
found.
Note (1) How to check the remote controllre
(a) Press the reset switch of the remote controller.
(b) If all LCD are displayed after zero (0) display, it is
basically normal.
Replace the display.
Control problem on
main unit
Is the unit
operable with remote
controller?
Normal
Defective remote
controller
NO
YES
(1)