Comfort timer setting
(a)
SKM model
If the timer is set at ON when the operation select switch is set at the cooling or heating, or the cooling or heating in auto
mode operation is selected, the comfort timer starts and determines the starting time of next operation based on the initial
value of 15 minutes and the relationship between the room temperature at the setting time (temperature of room temperature
sensor) and the setting temperature. (Max. 60 minutes)
Operation mode
Operation start time correction value (Min.)
3 < Room temp. – Setting temp.
1 < Room temp. – Setting temp.
≤
3
Room temp. – Setting temp.
≤
1
At cooling
+5
No change
–5
3 < Setting temp. – Room temp.
2 < Setting temp. – Room temp.
≤
3
Setting temp. – Room temp.
≤
2
At heating
+5
No change
–5
Notes (1) At 5 minutes before the timer ON time, operation starts regardless of the temperature of the room temperature sensor (Th1).
(2) This function does not actuate when the operation select switch is set at the dehumidifying as well as the dehumidifying in the auto mode.
However, the operation of item (1) above is performed during the dehumidifying in the auto mode.
(3) During the pleasant reservation operation, both the operation lamp and timer lamp illuminate and the timer lamp goes off after expiration of the timer, ON setting
time.
¡
If the difference (= Setting temperature – Room temperature) is 4ºC, the correction value is found to be +5 minutes from the
table shown above so that the starting time of next operation is determined as follows:
15 min. e 5 min. = 20 min. earlier
Current operation
Correction value
start time
Corrects the starting time of next operation by
calculating the temperature difference.
(Example) Heating
Setting temperature
Room temperature
Operation starting time
Time
Setting time
15 min.
10 min.
5 min.
earlier
earlier
earlier
(c)
Swing flap
Flap moves in upward and downward directions continuously.
Horizontal
blowing
(b) Memory flap (Excepted 22, 25models)
While the flap is operating if the AIRFLOW button is pushed once, it stops swinging at an angle.
As this angle is memorized in the microcomputer, the flap will be automatically set to the angle when next operation is
started.
◆
Recommendable stopping angle of the flap
Slant forward
blowing
COOL•DRY
HEAT
¡
Wall mounted type
¡
Ceiling recessed type
¡
Wall mounted type
¡
Ceiling recessed type
COOL•DRY
HEAT
Horizontal
blowing
Slant forward
blowing